–4–
Program feature or option
Permitted in
UL864? Y
/N
Possible settings
Settings permitted in UL 864
2
✱
24
DISPLAY TROUBLES OF
OTHER PARTITIONS
N
0 = disable
1 = enable
Must be set to “0” (disable) for
partition 1.
3
✱
01
EVENTS DISPLAY LOCK
N
0 = disable
1 = enable
Must be set to “1” (enable).
3
✱
12
ZN TYPE 18 DELAY USE
N
0 = disable
1 = enable
Must be set to “0” (disable).
3
✱
13 FIRE SUPERVISORY
RESPONSE TO OPEN/SHORT
(APPLIES TO ZONE TYPE 18)
N
0 = Trouble on open/Supv on short
1 = Supv on open/Supv on short
Must be set to “0”.
3
✱
14
WATERFLOW ALARM
SILENCE OPTION
N
0 = Silenced by User Code + OFF
1 = Silenced when zone restores
Must be set to “0” (Silenced by User
Code + OFF).
3
✱
16
DELAY FOR ZONE
TYPES 17 & 18
(Waterflow/Supervisory)
N
Enter 01-15 times 2 seconds
Enter 00 for no delay
Must be set to ‘00’ (no delay).
3
✱
18
EXTENDED DELAY FOR
ZONE TYPES 17 & 18 Multiplies
delay in 3*16 x 4)
N
0 = no extended delay
1 = multiply delay by 4
Must be set to ‘0’ (no extended
delay).
3
✱
19
AUXILIARY INPUT
ALTERNATE FUNCTION
ENABLE
N
0 = disable
1 = enable
Must be set to ‘0’ (disable).
3
✱
20
TRIGGER OUTPUTS
FUNCTION SELECTION
N
0 = remote keypad sounder
1 = keyswitch LEDs
Must be set to ‘0’ (remote keypad
sounder).
3
✱
21
MAXIMUM NUMBER OF
DIALER ATEMPTS
Y
1-8
Must be set at 3, 4 or 5.
3
✱
50
ZONE TYPE RESTORE
ENABLES FOR TYPES 16-18
N
0 = disable
1 = enable
Must be set to “1” (enable).
3
✱
55
RESET ON SECOND OFF
FOR BELL 1
N
0 = disable
1 = enable
Must be set to “0” (disable).
3
✱
56
RESET ON SECOND OFF
FOR BELL 2
N
0 = disable
1 = enable
Must be set to “0” (disable).
3
✱
57
BELL 2 AND AX RELAY
CONFIRM ARMING DING
N
0 = disable
1 = enable
Must be set to “0, 0” (disable).
3
✱
59
ENABLE BELL 2 &
AUXILIARY RELAY CHIME
ANNUNCIATION
N
0 = disable
1 = enable
Must be set to “0” (disable) if Bell 2
or Aux Relay is used for Fire.
3
✱
60 BELL 2 & AUX RELAY
TIMEOUT
Y
Enter 01-15 multiplied by 2 minutes.
00 = no timeout.
Must be set to “3” (Minimum of 6
minutes).
3
✱
82
BURGLARY FEATURES
ON PARTITION 1 ENABLE
N
0 = disable
1 = enable
Must be set to “0” (disable).
RESTRICTION FOR FIRE
RELAYS
Y Yes
No
Restriction for # 70 must be set to
Yes when programming fire relays.