– 10 –
*80
FOR TYPES 9, 10 and 14
9
10 14
1=enable; [0=disable]
Restores must be set to “1” for Commercial Fire installations.
*83
FIRST TEST REPORT TIME
| | |
[Day 00; hour 12; min 00]. Days 01-07, Hours 00-23, Min 00-
59; 00 in all boxes = instant (Day 01= Monday)
*84
SWINGER SUPPRESSION
[0, 0]
|
01-15
alarms
Must be "00" (disabled) for Commercial Burglary
*85
ENABLE DIALER REPORTS FOR PANICS & DURESS
1=enable;
[0=disable]
995
996
999
Duress
*87
ENTRY WARNING
[1]
1=continuous; 0=3 beeps
*88
BURG. ALARM COMM. DELAY
[0]
1=30 seconds; 0=no delay
Must be "0" for Commercial Burglary installations.
*89
ALARM
RESTORE REPORT TIMING
[0]
0 = Restore is sent when zone is restored or at disarming,
whichever occurs first.
1 = Restore is sent at disarming whether zone is restored or
not, or at bell timeout, but only if restored.
2 = Restore is sent at disarming, whether the zone is restored
or not.
This field applies only to Burglary zone types. It does not
apply to Fire or Panic zone types.
Must be "2" for Commercial Burglary installations.
*90
SEC. SUBS. ACCT #
| | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
2nd Page Programming Fields
(press *94)
1*12
PROGRAM NOTIFICATION SIGNAL
[1]
1=yes; 0=no
Must be "1" for Commercial Fire installations.
1*13
SYSTEM SENSOR REVERSING RELAY –
Not Used.
[0]
0=use neither Zone 1 or Zone 2 inputs; 1=use Zone 1 input;
2=use Zone 2 input; 3=use Zone 1 and Zone 2 inputs.
1*17
LOBBY PARTITION
[0]
Enter the "common lobby" partition (1-2)
1*18
AFFECTS LOBBY
[0]
Enter 1 if this partition affects the common lobby;
Enter 0 if it does not.
Must be "0" for Commercial Burglary and Commercial Fire
installations.
1*19
ARMS LOBBY
[0]
Enter 1 if arming this partition attempts to arm lobby;
Enter 0 if it does not.
Must be "0" for Commercial Burglary and Commercial Fire
installations.
1*20
EXIT ERROR LOGIC ENABLE
[0]
0=No; 1=Bypass E/E and Interior zones faulted after exit
delay.
Must be "0" for Commercial Burglary installations.
1*21
EXIT DELAY RESET
[0]
0=No; 1=Resets Exit Delay to programmed value after zone
is closed and then faulted prior to end of exit delay.
Must be "0" for Commercial Burglary installations.
FIELDS 1
✳
22-1
✳
25: Allow four sets of two zones each to be linked
so that both must fault within a 5-minute period to cause an alarm.
Default for these fields = [000], [000].
1*22
CROSS-ZONING PAIR ONE
| | | |
1*23
CROSS-ZONING PAIR TWO
| | | |
1*24
CROSS-ZONING PAIR THREE
| | | |
1*25
CROSS-ZONING PAIR FOUR
| | | |
1*26
PANIC BUTTON OR SPEEDKEY
[00, 00, 00, 00]
|
A
|
B
|
C
|
D
Enter speedkey macro # (01-32) to use keys A-C for macro.
Otherwise enter 00 to use as panic. For D key, enter macro
# 01-32, or 00 to select macro when key is pressed.
1*28
RF TX LOW BATTERY SOUND
[0]
1=immediate; 0=when disarmed
Must be
1
for UL installations.
1*29
RF TX LOW BATTERY REPORTING
[0]
1=enable;
0=disable
Must be
1
for UL installations.
1*30
RF RCVR CHECK-IN INTERVAL
[02]
|
02-15 times 2 hours; 00 disables supervision
Maximum is 2 (4 hr) for UL installations.
1*31
RF XMITTER CHECK-IN INTERVAL
[02]
|
02-15 times 2 hours; 00 disables transmitter supervision
Maximum is 2 (4 hr) for UL installations.
1*33
TOUCHTONE W/ROTARY BACKUP
[0]
1=enable;
0=disable
1*34
COMM. SPLIT REPORTING
[0]
0=no; 1=alarms and alarm restores primary, others
secondary; 2=open/close, test secondary, others primary;
3=fire alarms and fire restores to primary and secondary, all
others to secondary. See
✴
51 for comments if using with
dual reporting.
NOTE:
Split reporting should not be used with Dynamic
Signaling.
1*35
ACCESS CONTROL DIALER ENABLES
-
Not Used.
[0 0 0 0 0 0]
Trace
Trbl
Byp
Not Used
Syst
Alm
1=enable; 0=disable
Must Be Set To “0”.
1*42
CALL
WAITING DEFEAT
[0]
1=enable; 0=disable
1*43
PERM. KEYPAD BACKLIGHT
[0]
1=enable; 0=disable, when disabled, display lights when any
key is pressed, and turns off after period of keypad inactivity.