– 8 –
VISTA-32FB Programming Form
Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system,
see the
Partition-Specific Fields section for programming these fields. Standard default (*97) values are shown in brackets [ ];
otherwise, default = 0.
*00
INSTALLER
CODE
| | |
Enter 4 digits, 0-9 [5140]
*08
TEMPORAL SIREN PULSE -
Not Used at this time.
*09
ENTRY DELAY #1
[02]
|
00, 02-15 times 15 seconds
Maximum "03" for Commercial Burglary installations.
*10
EXIT DELAY #1
[03]
|
00, 03-15 times 15 seconds
Maximum "04" for Commercial Burglary installations.
*11
ENTRY DELAY #2
[06]
|
00, 02-15 times 15 seconds (must be longer than Entry Delay
#1). Maximum "03" for Commercial Burglary installations.
*12
EXIT DELAY #2
[08]
|
00, 03-15 times 15 seconds (must be longer than Exit Delay
#1). Maximum "04" for Commercial Burglary installations.
*13
BELL 1 TIMEOUT
[03]
|
01-15 times 2 minutes. Must be minimum 16 minutes for
Commercial Burglary installations. Must be minimum 6
minutes for Commercial Fire installations.
*15
KEYSWITCH ASSIGNMENT
[0]
Enter partition in which keyswitch used, 1-2; 9=silences
Notification Appliance Circuit if fire present; 0=disable
*16
BELL 1
CONFIRMATION OF ARMING DING [0]
1=enable; 0=disable.
NOTE: If using a keyfob, when the button is pressed, either for
arming or disarming, the bell will ding indicating that the button
is working.
Must be "1" for Commercial Burglary installations.
*17
AC LOSS KEYPAD SOUNDING
[1]
1=enable;
0=disable
Must be "1" for Commercial Fire installations.
*19
RANDOMIZE AC LOSS REPORT
[2]
0= within 2 minutes; 1=10-40 min; 2=1-3 hours; 3=6-12 hours
without Type 13, 1-3 hours with Type 13.
*20
VIP MODULE PHONE CODE -
N
ot used.
| |
Enter 01 - 09 for the first digit; enter
[00],
[11]
11 for “*” or 12 for “#” for the second digit.
Must be set to "00" for Commercial Burglary and Commercial
Fire installations.
*22
KEYPAD PANIC ENABLES
[001]
1=enable; 0=disable
995 996 999
NOTE:
Use for burglary panic types only. Do not use in
partition 1 in Fire systems.
*23
MULTIPLE ALARMS
[1]
1=enable;
0=disable
Must be “1” for Commercial Burglary installations
*24
IGNORE EXPANSION ZONE TAMPER
[0]
1=Ignore; 0=Enable tamper for RF and V-Plex.
Must be "0" for Commercial Burglary and Commercial Fire
installations if using these devices.
*25
BURG.TRIGGER FOR RESPONSE TYPE 8 [1]
1=enable;
0=disable
*26
INTELLIGENT
TEST
REPORTING
[0]
1=enable (no report sent if any other report was recently sent);
0=disable (send report at programmed interval, field *27)
Must be “0” for Commercial Burglary and Commercial Fire
installations.
*27
TEST REPORT INTERVAL
[0024
] | | |
Enter interval in hours, 0001-9999; 0000=no report;
Max. 0024 for Commercial Burglary and Commercial Fire
installations.
*28
POWER UP IN PREVIOUS STATE
[1]
1=enable;
0=disable
Must be “1” for Commercial Burglary and Commercial Fire
installations.
*29
QUICK ARM
[1]
1=enable;
0=disable
*30
MAIN DIALER TOUCHTONE OR ROTARY
[1]
1=TouchTone; 0=rotary
*31
PABX ACCESS CODE
| | | |
00-09; B-F (11-15)
*32
PRIM. SUBS. ACCT #
| | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
*33
PRIMARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2-second pause
*34
SECONDARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2-second pause