VISTA-20P/VISTA-15P

SUMMARY OF CONNECTIONS

V20P_V15P-SOC-V0

CLASS 2 PLUG-IN TRANSFORMER

16.5VAC, 25VA

(e.g. ADEMCO No. 1321).

(USE No. 1321CN IN CANADA)

TO 110VAC 

UNSWITCHED

OUTLET (24HR) 

–

+

THIS EQUIPMENT SHOULD BE INSTALLED
IN ACCORDANCE WITH THE NATIONAL
FIRE PROTECTION ASSOCIATION'S
STANDARD 72, CHAPTER 2 (NATIONAL
FIRE PROTECTION ASSOCIATION,
BATTERY-MARCH PARK, QUINCY,MA
02269).
PRINTED INFORMATION
DESCRIBING PROPER INSTALLATION,
OPERATION,TESTING, MAINTENANCE,
EVACUATION PLANNING AND REPAIR
SERVICE IS TO BE PROVIDED WITH THIS
EQUIPMENT.

24-HR BATTERY STANDBY REQUIRED FOR
FIRE INSTALLATIONS. USE 12V, 17.2AH
BATTERY FOR 600mA AUX POWER. SEE
INSTRUCTIONS.

BATTERY CAPACITY FOR EMERGENCY
BURGLARY STANDBY USE AT LEAST 4 HRS

USE UL LISTED LIMITED ENERGY
CABLE FOR ALL CONNECTIONS

USE 4300 / 1321X10 TRANSFORMER 
INTERFACE

 

IN PLACE OF 1321 OR

1321CN WHEN POWER LINE CARRIER
DEVICES ARE BEING USED. (SEE
INSTRUCTIONS FOR CONNECTIONS)

FOR COMPLETE

INFORMATION, SEE

INSTRUCTIONS K5305-1 

ALARM OUTPUT

10.5–13.8VDC, 2A MAX.

(600mA MAX. FOR UL

USAGE, INCLUDING

AUX POWER) STEADY

FOR BURGLARY/PANIC,

TEMPORAL PULSE

SOUNDING FOR FIRE.

CAN USE ADEMCO No. 702

SIREN, OR 12V BELL).

SEE INSTRUCTIONS. 

CHARGING VOLTAGE
13.8VDC. MAXIMUM
CHARGING CURRENT
650mA.

BATTERY

12V, 4AH

–

+

–

+

BLACK

RED

SEALED LEAD-ACID TYPE.
BATTERY NORMALLY NEED NOT BE
REPLACED FOR AT LEAST 3 YRS.

TO DETERMINE TOTAL STANDBY LOAD
ON BATTERY, ADD 100mA TO TOTAL OF
AUX. POWER OUTPUT AND REMOTE
KEYPAD CURRENTS. 

FLYING LEADS
FOR BATTERY
CONNECTION

CONNECTION OF THE FIRE ALARM
SIGNAL TO A FIRE ALARM
HEADQUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLY WITH THE
PERMISSION OF THE LOCAL AUTHORITY
HAVING JURISDICTION. THE BURGLAR
ALARM SIGNAL SHALL NOT BE
CONNECTED TO A POLICE EMERGENCY
NUMBER.

AUX. POWER

OUTPUT

10.5-13.8VDC

600mA MAX.

(500mA MAX.

FOR UL

OPTIONAL

FOR UP 

T

O

 40 ADDITIONAL ZONES

( FR

OM EITHER OR BO

TH GR

OUPS)

 

ADEMCO 5881* Type

RF RECEIVER

WIRELESS ZONES

*5882 IN CANADA

ADEMCO No. 4219

WIRED EXPANSION MODULE

(8 ADD'L EOLR WIRED ZONES)

-OR-

ADEMCO No. 4229

WIRED EXPANSION/RELAY MODULE

(8 ADD'L EOLR WIRED ZONES PLUS 2

OUTPUT RELAYS)

-OR-

ADEMCO No. 4204 RELAY MODULE

(4 OUTPUT RELAYS)

BLK
RED
GRN
YEL

1

2

3

7

8

11

12

17

20

21

22

23

24

25

EARTH 

GROUND

SEE 

INSTRUCTIONS

FOR PROPER
GROUNDING 

TELEPHONE WIRING

(VIA RJ31X* JACK AND DIRECT 

CONNECT CORD) 

*CA38A IN CANADA

DOC LOAD NO.: 3

BLA

CK:

 KEYP

AD GR

OUND (

-

 ) RETURN

RED:

 KEYP

AD PWR ( 

+

 )

GREEN:

 D

A

T

A

 IN FR

OM KEYP

AD

YELLO

W:

 KEYP

AD D

A

T

A

 OUT

REMOTE

KEYPADS

AND OTHER

ADDRESSABLE

DEVICES

(e.g. 5800TM,

4285/4286, LRR,

4219, 4229,
4204, 5881)

WARNING:

TO PREVENT RISK OF SHOCK,

DISCONNECT TELEPHONE LINE AT TELCO
JACK BEFORE SERVICING THIS UNIT.

BLK
RED

GRN

YEL

TO TERM 4
TO TERM 5
TO TERM 6
TO TERM 7

BLK
RED
GRN
YEL

AND/OR

RING

(GRAY)

TIP

(GREEN)

RING

(RED)

INCOMING

PHONE LINE

HANDSET

–

+

ZONE 1

ZONE 2

HI

LO

HI

LO

ZONE 3

ZONE 4

HI

LO

HI

LO

ZONE 5

ZONE 6

HI

LO

HI

LO

ZONE 7

ZONE 8

HI

LO

HI

LO

• 

MAXIMUM LOOP RESISTANCE: 

(EACH ZONE) 300 OHMS (PLUS EOLR)

• 
• RESPONSE, ZONES 1-8: 

10, 350, OR 700 MSEC (PROGRAMMABLE)

8-PIN CONNECTOR

USED FOR 4300/1321X10

TRANSFORMER

CONNECTIONS AND FOR

ON-BOARD TRIGGERS

SEE INSTRUCTIONS.

7 8

(USE SA4120XM-1

CABLE)

TIP

(BROWN)

}

}

THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO 
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.

COMPLIES WITH FCC RULES, PART 68.
FCC REGISTRATION NO. 5GBUSA-44003-AL-E
RINGER EQUIVALENCE: 0.1B.

WEEKLY TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS
SYSTEM. IN ADDITION, THIS SYSTEM MUST BE CHECKED BY A QUALIFIED
TECHNICIAN AT LEAST ONCE EVERY THREE (3) YEARS.

CAN BE USED FOR 2-WIRE SMOKE DETECT

ORS

RED JUMPER

CUT FOR BELL SUPERVISION.
ALSO, CONNECT 2000 OHM 
RESISTOR DIRECTLY ACROSS 
SOUNDER.

FOR CONNECTION OF OPTIONAL 4285 OR 4286 VIP 
MODULES TO PHONE TERMINALS, SEE INSTRUCTIONS.

ASSEMBLED IN MEXICO

5881L:    UP TO 8
5881M:   UP TO 16
5881H:   UP TO 64

INSTALLATIONS)

ALL OUTPUTS
ARE POWER
LIMITED.

NOTE:

KEYPAD (S)
CURRENT (IN
BOTH
PARTITIONS)
AND ALL
OTHER DEVICES
DRAWING
POWER FROM
TERMS 4 & 5
MUST BE
INCLUDED IN 
AUX CURRENT
DRAIN
CALCULATIONS.

}

2000 

OHMS

EOLR

2000 

OHMS

EOLR

2000 

OHMS

EOLR

2000 

OHMS

EOLR

2000 

OHMS

EOLR

2000 

OHMS

EOLR

2000 

OHMS

EOLR

2000 

OHMS

EOLR

SYNC

COM

DATA

TO
TRANS.

GND

+12 A

U

X

18

19

16

15

14

13

10

9

6

5

4

1 2 3 4

5

6

OUTPUT 18

(TRIG.

 2)

OUTPUT 17

(TRIG.

 1)

ALL DEVICES AND ACCESSORIES

USED IN A CANADIAN INSTALLATION

MUST BE LISTED FOR USE IN CANADA

BATTERY FUSE

FOR REPLACEMENT,
USE SAME VALUE
(e.g. ADEMCO No. 90-12)

3A

+

+

2000
OHMS
EOLR

HEAT

DETECTOR

RED

EOL

POWER

SUPERVISION

RELAY

MODULE

A77-716B

VIOLET

AUX PWR

OUTPUT

TERMINALS

5

4

_

_

+

_

BLK 

_

+

4-WIRE SMOKE

OR COMBUSTION

DETECTOR

TO ZONES 2-8

TERM. (  )

TO ZONES 2-8

TERM. (  )

RELAY

PROGRAM RELAY
AS ZONE TYPE 54
(FIRE ZONE RESET)

4-WIRE
SMOKE DETECTOR
CONNECTIONS

SET
RECEIVER’S
DIP SWITCH
FOR DEVICE
ADDRESS
OF “0”. 
SEE
INSTRUCTIONS.

SET UNIT’S
DIP SWITCH
FOR DEVICE
ADDRESSES
7 - 15
SEE
INSTRUCTIONS. 

MAXIMUM NUMBER OF 2-WIRE SMOKE DETECTORS ON ZONE 1 IS 16;
DETECTORS MUST HAVE COMPATIBILITY IDENTIFIER AS "A".

ZONE
PAIRS

2 / 10
3 / 11
4 / 12
5 / 13
6 / 14
7 / 15
8 / 16

TYPICAL WIRING FOR

ZONE DOUBLING

(VISTA-20P ONLY)

TYPICAL WIRING FOR

DOUBLE BALANCED ZONE

(VISTA-20P ONLY)

REMOTE KEYPADS

CAN USE 6150 OR 6160
KEYPADS.  LOCAL 
PROGRAMMING
MUST BE DONE WITH A
6139/6160, BUT NEED NOT
REMAIN IN THE SYSTEM
(SET TO ADDRESS 16).

13

12

14

10

11

6.2k

ZONE 10

3k

ZONE 2

2k

2k

2k

ZONE 3

2k

2k

2k

ZONE 4

TAMPER

CONTACTS

TAMPER

CONTACTS

VIST

A-20P ONL

Y

A D

IVISIO

N

 O
F

 PITTW

AY C

O

R

P

O

R

ATIO

N

165 E

ileen W

a

y

, S
y

osset, N

Y

  11791

C

opy

ri

ght ©

 2001 P

ittw
ay
 C
o

rporati

on

¬.35l

K5305-1PR  7/01

Содержание Ademco VISTA-15PCN

Страница 1: ...7 3 9 67 3 1 3URJUDPPLQJ XLGH ON OFF 1 OFF 4 MAX 7 INSTANT READY 2 AWAY 5 TEST 8 CODE 0 3 STAY 6BYPASS 9CHIME ARMED READY 1 OFF 4 MAX 7INSTANT READY 2 AWAY 5 TEST 8 CODE 0 3 STAY 6BYPASS 9CHIME ARMED READY K5305 1PR 7 01 ...

Страница 2: ...umbers for 5800 RF transmitters 57 Function Key Programming Unlabeled keypad keys known as ABCD keys for special functions 58 Zone Programming Same options as 56 mode but with fewer prompts Intended for those familiar with Expert mode this type of programming otherwise 56 mode is recommended 79 Output Device Mapping Assign module addresses and map individual relays powerline carrier devices 80 Out...

Страница 3: ...IMING 31 39 31 ONE AUDIBLE ALARM PER ZONE 0 0 no UL must be 0 1 yes 32 FIRE ALARMSOUNDER TIMEOUT 0 0 sounder stops at timeout 1 no sounder timeout UL must be 1 for fire install 33 ALARM SOUNDER TIMEOUT 1 0 none 1 4 min 2 8 min 3 12 min 4 16 min UL minimum 1 4 min 34 EXIT DELAY 70 70 Part 1 Part 2 00 99 seconds of exit delay time for each partition Common zones use same delay as partition 1 35 ENTR...

Страница 4: ...ll 5 All All 50 15 SEC DIALER DELAY BURG 0 0 no UL must be 0 1 yes 53 SECOA RADIONICS SELECT 0 0 Radionics 0 9 B F 1 SESCOA 0 9 only reporting Select 0 for all other formats 54 DYNAMIC SIGNALING DELAY 0 Delay selectable from 0 to 225 secs in 15 sec increments 0 no delay both signals sent 1 15 secs 2 30 secs etc UL must be 0 55 DYNAMIC SIGNALING PRIORITY 0 0 Primary Dialer first 1 Long Range Radio ...

Страница 5: ...de 86 CANCEL VERIFY 0 0 no 1 yes 87 MISC FAULT DELAY TIME used with Configurable Zone Types digit 6 0 0 15 seconds 6 2 1 2 min 12 8 min 1 30 seconds 7 3 min 13 10 min 2 45 seconds 8 4 min 14 12 min 3 60 seconds 9 5 min 15 15 min 4 90 seconds 10 6 min 5 2 minutes 11 7 min UL may only be used on non burglar alarm non fire alarm zones when used in fire and or UL burglar alarm installation 89 EVENT LO...

Страница 6: ...EPORTING OPTIONS 0 0 0 Part 1 Part 2 common See field 162 for reporting options Select for each partition use zone list 10 if using options 12 or 13 166 PAGER 3 PHONE No Enter up to 20 digits 0 9 11 12 13 2 second pause 167 PAGER 3 CHARACTERS Enter the optional prefix characters up to 16 digits 0 9 11 12 13 2 second pause 168 PAGER 3 REPORTING OPTIONS 0 0 0 Part 1 Part 2 common See field 162 for r...

Страница 7: ...o this zone type Enter the codes sequentially all 6 digits When entering digits moves cursor back moves forward Press when done to continue KEYPAD OPTIONS 190 196 NOTE Options for keypad address 16 are set by the factory and cannot be changed NOTE Each keypad must be assigned a unique address Keypads programmed with the same address will give unpredictable results 190 KEYPAD 2 ADDRESS 17 0 0 Parti...

Страница 8: ...ms when armed disarmed 1 don t show alarms when armed show alarms trbles faults when disarmed 3 never show any alarms trbles faults 0 no 4 power reset after fault by code OFF 12 verification see zone type 16 0 no 1 delay 1 2 delay 2 0 no 4 use exit delay 0 no 8 yes see note 2 Digit 7 fault display power reset verification Digit 8 entry delay 1 entry delay 2 exit delay interior zone type DIGIT 9 DI...

Страница 9: ...6 37 38 39 40 41 42 43 44 45 46 47 48 49 1 BR 50 1 BR 51 1 BR 52 1 BR 53 1 BR 54 1 BR 55 1 BR 56 1 BR 57 1 BR 58 1 BR 59 1 BR 60 1 BR 61 1 BR 62 1 BR 63 1 BR 64 1 BR 95 00 N A N A N A N A keypad 1 96 00 N A N A N A N A keypad 3 99 06 N A N A N A N A keypad NOTES Zone Type see chart on page 12 Input Type HW 1 zones 1 8 AW 2 zones 9 48 RF 3 zones 1 48 UR 4 zones 1 48 BR 5 zones 49 64 Response Time 0...

Страница 10: ... X10 Output No Module Addr Pos 1 4 Unit No Description Output No Module Addr Pos 1 4 Unit No Description 01 09 02 10 03 11 04 12 05 13 06 14 07 15 08 16 17 On Board Trigger 1 18 On Board Trigger 2 81 ZONE LISTS FOR OUTPUT DEVICES Fill in the required data on the worksheet below and follow the procedure in the installation manual as you enter the data during the displays and prompts that appear in ...

Страница 11: ... 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 ZONE TYPE SYSTEM OPERATION Choices for Zone Types are 00 Not Used 05 Trouble Day Alarm Night 10 Interior w Delay 24 Silent Burglary 01 Entry Exit 1 06 24 Hr Silent 12 Monitor Zone 77 Keyswitch 02 Entry Exit 2 07 24 Hr Audible 14 Carbon Monoxide 90 93 Configurable 03 Perimeter...

Страница 12: ... central station and provides an alarm sound at the keypad and an audible external alarm Type 08 24 hour Auxiliary Alarm Assign to a zone containing an emergency button or to a zone containing monitoring devices such as water or temperature sensors Sends a report to the central station and provides an alarm sound at the keypad No bell output is provided Type 09 Fire Provides a fire alarm on short ...

Страница 13: ...eyswitch Types 90 93 Installer Defined These zone types can be programmed for various custom responses See data fields 182 185 UL Zone types 90 93 may not be used as fire or burglar zones in fire or UL burglar alarm installations The system can still be armed when these zone types are in a faulted condition Schedules installer code 6 4 master code can only access schedules 01 16 for VISTA 20P 01 0...

Страница 14: ...7 PERIMETER 148 PHONE 150 POINT 151 POLICE 152 POOL 153 POWER R 155 RADIO 156 REAR 157 RECREATION 159 REFRIGERATION 160 RF 161 RIGHT 162 ROOM 163 ROOF S 164 SAFE 165 SCREEN 166 SENSOR 167 SERVICE 168 SHED 169 SHOCK 170 SHOP 171 SHORT 173 SIDE 174 SKYLIGHT 175 SLIDING 176 SMOKE 178 SONS 179 SOUTH 180 SPRINKLER 182 STATION 184 STORE 185 STORAGE 186 STORY 190 SUPERVISED 191 SUPERVISION 192 SWIMMING 1...

Страница 15: ...w 5804BD ENROLL AS BR LOOP 3 LOOP 1 LOOP 2 LOOP 4 SET HOUSE CODE YOU MUST ENROLL THIS BUTTON LOOP 3 LOOP 1 LOOP 2 LOOP 4 YOU MUST ENROLL THIS BUTTON LOOP 1 5809 ENROLL AS RF LOOP 2 REED Table of Device Addresses Address Report Device Programmed by 00 100 RF Receiver 56 zone programming input device type entry 03 103 Long Range Radio automatic if output to long range radio field 29 enabled 04 104 4...

Страница 16: ... RING GRAY TIP GREEN RING RED INCOMING PHONE LINE HANDSET ZONE 1 ZONE 2 HI LO HI LO ZONE 3 ZONE 4 HI LO HI LO ZONE 5 ZONE 6 HI LO HI LO ZONE 7 ZONE 8 HI LO HI LO MAXIMUM LOOP RESISTANCE EACH ZONE 300 OHMS PLUS EOLR RESPONSE ZONES 1 8 10 350 OR 700 MSEC PROGRAMMABLE 8 PIN CONNECTOR USED FOR 4300 1321X10 TRANSFORMER CONNECTIONS AND FOR ON BOARD TRIGGERS SEE INSTRUCTIONS 7 8 USE SA4120XM 1 CABLE TIP ...