5800 Series Transmitter Input Loop Identification
•
All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes.
Each
of the inputs requires its own programming zone
(e.g., a 5804's four inputs require four programming zones).
•
Transmitter inputs entered as:
"RF" (Supervised RF) Type
send periodic check-in
signals, as well as fault, restore and low battery signals.
The transmitter must remain within the receiver's range.
“UR" (Unsupervised RF) Type
send all the signals that
the "RF" Type does, but the control does not supervise
the check-in signals. The transmitter may, therefore, be
carried off-premises.
"BR" (Unsupervised Button RF) Type
only send fault
signals. They do not send restore or check-in signals.
They will indicate a low battery condition when tested or
activated normally. The transmitter may be carried off-
premises.
Note
: For information on any transmitter not shown
above, refer to the instructions accompanying that
transmitter for details regarding loop numbers, etc.
UL NOTE
:
The 5802MN, 5802MN2, 5804,
5804BD, 5814, 5816TEMP, 5819,
5819WHS & BRS, 5827BD, and 5850
transmitters are not intended for use
in UL installations
5 8 0 1
ENROLL AS "UR" OR "RF"
LOOP
1
5 8 0 2 M N
ENROLL AS "UR" OR "RF"
YOU MUST
ENROLL THIS
BUTTON
LOOP 3
LOOP 1
LOOP 2
LOOP 4
LOOP
1
5808
ENROLL AS "RF"
5 8 0 4
ENROLL
AS "BR"
5 8 1 7
ENROLL AS "RF"
LOOP
1
(PRIMARY)
2
(AUX. CENTER)
3
(AUX. RIGHT)
LOOP
1
(MOTION)
5 8 9 0
ENROLL AS "RF"
5 8 1 6
ENROLL AS "RF"
LOOP
2
(REED)
LOOP 1
(TERMINALS)
5 8 2 7
SET HOUSE CODE
5 8 2 7 B D
SET HOUSE CODE
5 8 1 6 M N
ENROLL AS "RF"
LOOP
2
(REED)
LOOP 1
(TERMINALS)
5 8 1 9
ENROLL AS "RF"
LOOP
2
(REED)
LOOP 1
(TERMINALS)
ALTERNATE
POSITION
FOR LOOP2
LOOP 3
(TERMINALS)
5 8 1 9 S ( W H S & B R S )
ENROLL AS "RF"
LOOP
2
(REED)
LOOP 1
(INTERNAL
SHOCK
SENSOR)
LOOP 3
(TERMINALS)
5 8 5 0 ( G B D )
ENROLL AS "RF"
(Green)
(Red)
(Yellow)
5 8 0 4 B D
ENROLL AS "BR"
•
•
•
•
•
••
•
•
•
•
•
•
•
•
•
• •
•
LOOP 3
LOOP 1
LOOP 2
LOOP 4
SET
HOUSE
CODE
YOU MUST
ENROLL THIS
BUTTON
LOOP 3
LOOP 1
LOOP 2
LOOP 4
YOU MUST
ENROLL THIS
BUTTON
LOOP
1
5809
ENROLL AS "RF"
LOOP 2
(REED)
Table of Device Addresses
Address
Report
††
Device
Programmed by…
00
100
RF Receiver
*56 zone programming: input device type entry
03
103
Long Range Radio
automatic if output to long range radio field *29 enabled
04
104
4286 Voice Module
automatic if phone module access code field *28 enabled
Zone Expanders (4219/4229):
*56 zone programming: input device type entry, then:
07
107
module 1 zones 09 - 16
•
automatic if zone no. 9-16 entered as AW type or relay assigned
08
108
module 2 zones 17 - 24
•
automatic if zone no. 17-24 entered as AW type or relay assigned
09
†
109
module 3 zones 25 - 32
•
automatic if zone no. 25-32 entered as AW type or relay assigned
10
†
110
module 4 zones 33 - 40
•
automatic if zone no. 33-40 entered as AW type or relay assigned
11
†
111
module 5 zones 41 - 48
•
automatic if zone no. 41-48 entered as AW type or relay assigned
Relay Modules (4204):
*79 output device programming: device address prompt:
12
112
module 1
•
entered at device address prompt
13
113
module 2
•
entered at device address prompt
14
†
114
module 3
•
entered at device address prompt
15
†
115
module 4
•
entered at device address prompt
Keypads:
data filed programming as listed below:
16
n/a
keypad 1
•
always enabled for partition 1, all sounds enabled.
17
n/a
keypad 2
•
data field *190
18
n/a
keypad 3
•
data field *191
19
n/a
keypad 4
•
data field *192
20
n/a
keypad 5
•
data field *193
21
n/a
keypad 6
•
data field *194
22
n/a
keypad 7
•
data field *195
23
n/a
keypad 8
•
data field *196
28
n/a
5800TM Module
automatic
† These module addresses apply to VISTA-20P only.
††
Addressable devices are identified by “1” plus the device address when reporting. Enter report code for zone 91 to enable
addressable device reporting (default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification
touchpad display options.