Honeywell 4000 Series Скачать руководство пользователя страница 9

OPERATION

Each time actuator terminals T5-T6 are (re)powered, the micro-
processor will cycle the valve through a full stroke to calibrate its
position. Any stroke between 1/2

 (13 mm) and 1

” 

(25 mm) will be

divided into 30 equal steps. Run time is proportional to stroke length
and power supply voltage. The actuator will also slow down as the
valve closes off the seat. The LED lights when terminals T5-T6 are
powered, and flashes when the actuator is in motion. T5 is con-
nected to Terminal R in ML6984 and to Terminal W in ML7984.

Initial  callibration  does  not  apply  to  ML6984  installed  for  3-wire
control or installed for 5-wire control without the 272630D position
feedback/auxiliary switch module. Span and start positions will need
to be set during controller set-up. See ML6984 Operation 3-wire,
below.

ML7984  Operation:

The  microprocessor  responds  to  the  signal  across  the  input
terminals based on the configuration DIP switch settings.

When correctly connected to the actuator, a control signal between
signal input terminals is converted to a digital run time and compared
to pulse counts from the first gear in the gear train. When these
counters are equal, the drive motor and drive shaft are stationary.

As  long  as  the  value  of  the  controlled  medium  remains  at  the
controller setpoint, the control loop circuit is in balance, and the
actuator does not run. When the controller set point or controlled
temperature  changes,  the  controller  output  voltage  is  changed,
causing the counters to differ. As the actuator moves in the direction
to  correct  the  difference,  the  counters  increment  or  decrement,
and stop the actuator when the input and gear counts agree.

At the end of the valve stroke, the actuator develops the necessary
force  for  positive  valve  close-off. The  motor  stops  automatically
when the motor draws a predetermined current which corresponds
to a force level. The digital counters are reset and calibrated at
each end of stroke.

Modulating  actuators  will  automatically  travel  to  the  position
corresponding to analog input signal following the self-calibration
cycle.

1. Disconnect power supply before beginning installation to prevent
electrical shock and equipment damage.
2. All  wiring  must  comply  with  applicable  local  electrical  codes,
ordinances, and regulations.
3. Make certain that the voltage and frequency of the power supply
correspond to the rating of the device.
4. 

DO  NOT  electrically  operate  the  MLx984  actuator  before

assembly to the valve because damage not apparent to the
installer may occur.

5.

 DO NOT connect  24 Vac between any ML7984 signal input

terminals. DEVICE FAILURE WILL RESULT!

  

!

 

NOTE:

  

!

 

Caution

GENERAL NOTE:

1. The ML7984 must be field configured with the DIP switches which

are located beside the terminal block. See wiring diagrams for
details. Turn power off before setting the DIP switches.

2. There is a 1.5 second delay in actuator response to every signal

change. This occurs to screen out electrical noise.

3. For proper operation, voltage on the T5 and T6 must not be less

than 22 Vac or 24 Vdc during running or  force generating stages.
Increase  transformer  VA  rating  or  use  a  model  with  better
regulation if voltage drops below 22 Vac when the valve is closing
off.

ML6984 Floating Operation, 5-Wire:

The motor is controlled by a microprocessor. Connecting B to R for
1/10 second or longer tells the microprocessor to cause the actua-
tor to drive upwards. Connecting W to R will cause the actuator to
drive downwards. For “floating” control, the actuator will remain in
the last position when  there is no connection to R.

At the end of the valve stroke, the actuator will develop the neces-
sary force for positive valve close-off. As forces are developed, the
current to the motor increases. The microprocessor stops the ac-
tuator automatically when motor current and force reaches the fac-
tory-calibrated level.

There  must  be  at  least  1.5  second  delay  between  successive
floating input signals. The  actuator will ignore floating signals during
calibration cycle and does not remember any pulses sent during
this  period.  The  controller  may  need  to  run  through  its  own
calibration cycle before use.

ML6984 Operation, 3-Wire:

ML6984  may  be  installed  like  a  conventional  (non-electronic)
floating actuator. The interface electronics are powered at the same
time  as  the  motor.  Pulses  must  be  at  least  100  ms  long  with  a
delay of at least 1500 ms between pulses. When ML6984 is not
powered between terminals T6 and T5/R, self-calibration will not
occur. 

The controller must drive the valve through a cycle manually

to calibrate stroke to the controller.

The  272630D  position  feedback/auxiliary  switch  module  cannot
be used with ML6984 3-wire installation. The 272630D requires
continuous power.

ML6984 XL10 Controller Compatibility:

XL10 controllers are designed to work with constant-speed actua-
tors. ML6984 actuators use direct current motors which vary their
speed as the valve seats or if power supply voltage is not consist-
ent. ML6984 actuators in 5-wire mode offer 30 discrete positions
only.  To  minimize  potential  valve  position  drift,  XL10  controllers
should use the 3-wire installation and be programmed for a daily
valve exercise cycle.

  

!

 

NOTE:

  

!

 

NOTE:

9

95C-10939-4

Содержание 4000 Series

Страница 1: ...ple actuators and controllers 24 Vac or 28 Vdc power supply Field addable position feedback auxiliary switch module avail able APPLICATION The ML6984 and ML7984 are self contained self adjusting motorized valve actuators that mount directly onto V5011 two way and V5013 three way globe valves providing linear stem operation between 13 mm 1 2 and 25 mm 1 ML6984 is for use with low voltage SPDT Serie...

Страница 2: ... Stem Coupling 1 4 28 UNF thread Stroke Timing Nominal 63 seconds for 3 4 stroke Proportional to stroke length at 24 Vac Closing Force 710 N 160 lbs minimum at 24 Vac Force varies 22 N V 5 lbf volt Performance Specifications Life Expectancy at rated load and power conditions 50 000 full stroke cycles plus 1 000 000 repositions of 10 stem travel or 10 years whichever occurs first Hysteresis 5 Short...

Страница 3: ...r rubber O ring over the valve stem Fig 3 Indicator will self align to the marking on the yoke after complete operating cycle FIG 2 MINIMUM MOUNTING CLEARANCE When Installing This Product 1 Read these instructions carefully Failures to follow them could damage the product or cause a hazardous condition 2 Check ratings given in instructions and on the product to ensure the product is suitable for y...

Страница 4: ...astic cover from the MLx984 by loosening the two captive screws located on the top Drop the Allen Hex type of set screw included in the plastic bag into the top of the shaft hex side up 6 Tighten the set screw to lock valve stem in place Fig 6 using a 1 8 Allen wrench included FIG 4 U BOLT ASSEMBLY NOTE Use U bolt supplied with actuator Do not replace with stainless steel U bolt on chilled water v...

Страница 5: ...4 WITH XL10 ELECTRONIC CONTROLLER For Figures 8A 8B and 8C the following apply 1 2 3 4 5 Power supply provides overload protection and disconnect means Allow up to 0 5 amps for each device Actuators and controller can share same transformer provided that the VA rating of the transformer is not exceeded and proper phasing is observed Do not mix a c and d c power sources Controller can be low voltag...

Страница 6: ... c power sources In ML7984 T5 and W terminals are connected internally Device is compatible with 3 conductor wiring Use configuration DIP switches to select device functions Direct acting function actuator stem moves downwards with signal increases to 10V 20mA or Reverse acting function actuator stem moves upwards with signal increases to 10V 20mA Always turn power off before setting the DIP switc...

Страница 7: ...n DIP switches to select device functions Direct acting function actuator stem moves upwards with signal increase or Reverse acting function actuator stem moves downwards with signal increase Turn power off before setting the DIP switches For common transformer and common controller application please consult the factory For Figure 10A Only Maximum resistance per control circuit of 280 For Figure ...

Страница 8: ...function actuator stem moves upwards with signal increases to 10V 20mA or Reverse acting function actuator stem moves downwards with signal increases to 10V 20mA Turn power off before setting the DIP switches 1 2 3 4 5 8 95C 10939 4 4 5 T6 T5 B R W 3 2 ML7984 T6 T5 B R W 1 L1 L2 OR 28 Vdc 24 Vac T5 T6 3 2 ML7984 3 2 ML7984 T6 T5 B R W R W R W R W ELECTRONIC SERIES 90 W973 T775 H775 W7100 NOTE Pola...

Страница 9: ... the installer may occur 5 DO NOT connect 24 Vac between any ML7984 signal input terminals DEVICE FAILURE WILL RESULT NOTE Caution GENERAL NOTE 1 The ML7984 must be field configured with the DIP switches which are located beside the terminal block See wiring diagrams for details Turn power off before setting the DIP switches 2 There is a 1 5 second delay in actuator response to every signal change...

Страница 10: ...e needed Use Resistor Kit Part 272822 and set DIP switches accordingly See Figures 12 13 TO REPLACE ML684 1 The new ML6984 is a direct replacement for the old ML684A in single actuator or parallel multiple actuators hook up The old and new actuators can be mixed in the same electrical circuit For multiple actuators controlled by a common controller in parallel these actuators must be wired so that...

Страница 11: ...ke sure the valve stem is locked in place with the set screw 3 Connect 24 Vac or 28 Vdc power to T5 and T6 4 Jumper R B The valve stem should move up 5 Jumper R W The valve stem should move down 6 For Floating operation open R connection Valve stem should remain in position 7 Re connect all control wiring 8 Operate the system valve actuator and controller for several cycles to ensure proper instal...

Страница 12: ...ge No or low power supply 1 Check power supply 2 Check callibration cycle 3 Valve stroke length less than 1 2 or greater than 1 1 4 4 Reset device by a momentary disconnect of power at T5 and T6 Check voltage on T5 T6 terminals Change DIP switch setting ML7984 in mA mode with voltage input Signal degradation due to incompatible load impedance Output and ML Input Impedance specifications Galvanic r...

Отзывы: