Honeywell 4000 Series Скачать руководство пользователя страница 10

ML6984 On-Off Operation:

For on-off operation, ML6984 requires a 24 Vac SPDT contact.
An  interface  relay  such  as  RA889  is  required  to  power  the
anticipator heater of an electromechanical thermostat such as
T87F. Please refer to Figure 12.

See  Fig.  13,  if  connecting  TH5110D  or  TH6110D  FocusPRO

TM

thermostats to ML6984. Configure the thermostats for Series 20
operation.

T5

T6

B

W

R

R

W

ML6984

1K

1K1

2

SET HEATING ANTICIPATOR TO MATCH CURRENT DRAW OF RELAY 1K. 
DO NOT ROUTE RELAY CONTACTS THROUGH THERMOSTAT.

1

L1

L2

2

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.

FIG. 12 

 ML6984 WITH Honeywell Round

TM 

THERMOSTAT

If  connecting  the  ML6984  directly  to  a T87F  with  a  Series  20
sub-base, 

clip out the cooling anticipation resistor

 on the sub-

base between terminals R

c

 

and Y. This is needed for electrical

compatibility  with  ML6984  but  may  result  in  wider  room
temperature swings due to the loss of anticipation.

FIG. 13 — ML6984 WITH FocusPRO

TM

 ELECTRONIC

THERMOSTAT

REPLACEMENT NOTES

TO REPLACE ML784 or ML984:

1.  The  old  ML784  or  ML984  actuators  cannot  be  used  with  new

ML7984 valve actuators in the same circuitry, unless the old models
are each powered by their own transformer to prevent cross-talking.

2. The ML7984 is a direct replacement for all old ML784 and ML984,

except:

a)  When  replacing  the  old  reverse  acting  models,  the  signal  input

wires to the new devices no longer need to be reversed. Just follow
the terminal polarity designations and DIP switch settings.

b) When replacing the old actuator which has an Electronic Series 90

“Supermod” controller - e.g.: T775, W973, H775, W7100 - the old
interface resistor must be removed. The ML7984 Series 4000 will
work directly with the controller without the external 240

!

  resistor.

c)  When  replacing  the  old  ML784  (mA  model)  in  multiple-actuator

installations,  resistor(s)  will  be  needed.  Use  Resistor  Kit  (Part
#272822) and set DIP switches accordingly. See Figures 12 & 13.

TO REPLACE ML684:

1. The new ML6984 is a direct replacement for the old ML684A in

single actuator or parallel multiple actuators hook-up. The old and
new  actuators  can  be  mixed  in  the  same  electrical  circuit.  For
multiple  actuators  controlled  by  a  common  controller  in  parallel,
these actuators must be wired so that they all travel in the same
direction.

2. When replacing the ML684A1009 (80 lbf) with this new ML6984 on

the V5045 valve, the installed valve adaptor (part # 272629A) on
the valve stem and actuator assembly is still needed.

TO REPLACE ML6874:

1. The ML6984 is a direct replacement for the old ML6874 in

single actuator hook-up.

2.  For  parallel,  multiple  ML6874  actuators  applications,  an

isolation  relay  must  be  used.  The  isolation  relay  contacts
should  be  placed  in  the  new  ML6984  actuator  signal  input
“W” and “B” circuit.

TO REPLACE LINE VOLTAGE AUXILIARY
SWITCHES:

These accessories are no longer available. Replace the old
actuator with new model and 272630D position feedback/
auxiliary switch module.

Operate an external relay, such as R8845U, using the adjust-
able SPDT pilot duty output on the 272630D.

If a second, independent output switch is needed, wire the
2-10 Vdc position feedback signal to an Approved, adjustable,
voltage-controlled relay.

10

95C-10939-4

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND 
OVERLOAD PROTECTION AS REQUIRED.

FACTORY INSTALLED JUMPER.

OPTIONAL 24 VAC COMMON CONNECTION.

CONFIIGURE SYSTEM TYPE TO HEAT ONLY IN THE INSTALLER SETUP.

TERMINALS R AND T5 ARE INTERNALLY CONNECTED.

1

2

3

4

5

R

C

1

L1

(HOT)

L2

ML6984

3

4

2

O/B

TH5110D

TH6110D

Rc

R

Y

C

W

G

B

W

R

T6

T5

5

POWER TO OPEN
AND POWER TO 
CLOSE
MOTOR OR VALVE
(SERIES 20)

THERMOSTAT WIRING TERMINALS

The 272630D position feedback/auxiliary switch module
cannot be used with ML6984 3-wire installation. The 272630D
requires continuous power.
The ML6984 5-wire installation recalibrates its position each
time terminals T5 and T6 are (re)powered when  272630D is
installed.

  

!

 

NOTE:

Содержание 4000 Series

Страница 1: ...ple actuators and controllers 24 Vac or 28 Vdc power supply Field addable position feedback auxiliary switch module avail able APPLICATION The ML6984 and ML7984 are self contained self adjusting motorized valve actuators that mount directly onto V5011 two way and V5013 three way globe valves providing linear stem operation between 13 mm 1 2 and 25 mm 1 ML6984 is for use with low voltage SPDT Serie...

Страница 2: ... Stem Coupling 1 4 28 UNF thread Stroke Timing Nominal 63 seconds for 3 4 stroke Proportional to stroke length at 24 Vac Closing Force 710 N 160 lbs minimum at 24 Vac Force varies 22 N V 5 lbf volt Performance Specifications Life Expectancy at rated load and power conditions 50 000 full stroke cycles plus 1 000 000 repositions of 10 stem travel or 10 years whichever occurs first Hysteresis 5 Short...

Страница 3: ...r rubber O ring over the valve stem Fig 3 Indicator will self align to the marking on the yoke after complete operating cycle FIG 2 MINIMUM MOUNTING CLEARANCE When Installing This Product 1 Read these instructions carefully Failures to follow them could damage the product or cause a hazardous condition 2 Check ratings given in instructions and on the product to ensure the product is suitable for y...

Страница 4: ...astic cover from the MLx984 by loosening the two captive screws located on the top Drop the Allen Hex type of set screw included in the plastic bag into the top of the shaft hex side up 6 Tighten the set screw to lock valve stem in place Fig 6 using a 1 8 Allen wrench included FIG 4 U BOLT ASSEMBLY NOTE Use U bolt supplied with actuator Do not replace with stainless steel U bolt on chilled water v...

Страница 5: ...4 WITH XL10 ELECTRONIC CONTROLLER For Figures 8A 8B and 8C the following apply 1 2 3 4 5 Power supply provides overload protection and disconnect means Allow up to 0 5 amps for each device Actuators and controller can share same transformer provided that the VA rating of the transformer is not exceeded and proper phasing is observed Do not mix a c and d c power sources Controller can be low voltag...

Страница 6: ... c power sources In ML7984 T5 and W terminals are connected internally Device is compatible with 3 conductor wiring Use configuration DIP switches to select device functions Direct acting function actuator stem moves downwards with signal increases to 10V 20mA or Reverse acting function actuator stem moves upwards with signal increases to 10V 20mA Always turn power off before setting the DIP switc...

Страница 7: ...n DIP switches to select device functions Direct acting function actuator stem moves upwards with signal increase or Reverse acting function actuator stem moves downwards with signal increase Turn power off before setting the DIP switches For common transformer and common controller application please consult the factory For Figure 10A Only Maximum resistance per control circuit of 280 For Figure ...

Страница 8: ...function actuator stem moves upwards with signal increases to 10V 20mA or Reverse acting function actuator stem moves downwards with signal increases to 10V 20mA Turn power off before setting the DIP switches 1 2 3 4 5 8 95C 10939 4 4 5 T6 T5 B R W 3 2 ML7984 T6 T5 B R W 1 L1 L2 OR 28 Vdc 24 Vac T5 T6 3 2 ML7984 3 2 ML7984 T6 T5 B R W R W R W R W ELECTRONIC SERIES 90 W973 T775 H775 W7100 NOTE Pola...

Страница 9: ... the installer may occur 5 DO NOT connect 24 Vac between any ML7984 signal input terminals DEVICE FAILURE WILL RESULT NOTE Caution GENERAL NOTE 1 The ML7984 must be field configured with the DIP switches which are located beside the terminal block See wiring diagrams for details Turn power off before setting the DIP switches 2 There is a 1 5 second delay in actuator response to every signal change...

Страница 10: ...e needed Use Resistor Kit Part 272822 and set DIP switches accordingly See Figures 12 13 TO REPLACE ML684 1 The new ML6984 is a direct replacement for the old ML684A in single actuator or parallel multiple actuators hook up The old and new actuators can be mixed in the same electrical circuit For multiple actuators controlled by a common controller in parallel these actuators must be wired so that...

Страница 11: ...ke sure the valve stem is locked in place with the set screw 3 Connect 24 Vac or 28 Vdc power to T5 and T6 4 Jumper R B The valve stem should move up 5 Jumper R W The valve stem should move down 6 For Floating operation open R connection Valve stem should remain in position 7 Re connect all control wiring 8 Operate the system valve actuator and controller for several cycles to ensure proper instal...

Страница 12: ...ge No or low power supply 1 Check power supply 2 Check callibration cycle 3 Valve stroke length less than 1 2 or greater than 1 1 4 4 Reset device by a momentary disconnect of power at T5 and T6 Check voltage on T5 T6 terminals Change DIP switch setting ML7984 in mA mode with voltage input Signal degradation due to incompatible load impedance Output and ML Input Impedance specifications Galvanic r...