Honeywell 4000 Series Скачать руководство пользователя страница 5

WIRING SCHEMATICS

MLx984 actuators are designed to operate from a Safety Extra Low Voltage, Class II power source. A 7/8

 wiring hole is provided for

attaching flexible conduit where required by local codes. When installing outdoors, weatherproof conduit fittings approved for outdoor
and wet locations must be used.

  

!

 

Caution

Electrical Shock or Equipment Damage Hazard. Can Shock Individuals or Short Equipment Circuitry.

Disconnect power supply to the actuator to prevent electrical shock and equipment damage, or remove and cap the air line to the
actuator.

  

!

 

Note

In all cases when wiring multiple actuators, the power supply to all actuators must be connected in a “star” fashion to reduce exces-
sive voltage drop. DO NOT “daisy chain” i.e. connect power to one actuator then branch to another.

Operation:

The recommended valve actuator power source is a Safety Extra-Low Voltage (SELV) Class II, 24 V transformer or regulated 28 Vdc
across terminals T5 & T6. Internal circuitry provides dc power for the electronic sensing and drive motor circuits.

 

FIG. 8C — 5-WIRE CONTROL OF ML6984

FIG. 8B — 3-WIRE CONTROL OF ML6984 WITH XL10

ELECTRONIC CONTROLLER

For Figures 8A, 8B, and 8C the following apply:

1

2

3

4

5

Power supply provides overload protection and disconnect means.

Allow up to 0.5 amps for each device. Actuators and controller can share same transformer, provided that the VA rating of the
transformer is not exceeded and proper phasing is observed. 

Do not mix a.c. and d.c. power sources.

Controller can be low voltage SPDT Series 20 “on-off” or SP3T Series 60 “floating” (tri-state) type. Terminals R and T5 are
connected inside the ML6984.

Multiple actuators controlled by a common controller in parallel must be wired so that they all travel in the same direction.
Reverse acting actuators will NOT operate reliably in combination with direct acting units due to gearbox tolerances. Use
ML7984 modulating actuators, or dedicated controllers, or separate controller outputs for each group instead.

5-wire installation is required with the 272630D position feedback/auxiliary switch module.

5

95C-10939-4

FIG. 8A — 3-WIRE CONTROL OF ML6984 WITH

SERIES 60 CONTROLLER

W

B

R

3

4

4

2

1

W

W

R

R

B

B

24 Vac

T5

T5

T5

T6

T6

T6

28 Vdc

OR

L1

L2

ML6984

Typical SPDT Controller

ML6984

Typical Electro-mechanical

Controller

1

2

3

R

W

B

W

B

R

T6

T5

ML6984

L1

L2

24 Vac

1

3

1

3

2

W

R

B

T6

T5

C

H

ML6984

Typical Electronic 

Controller

L1

L2

Содержание 4000 Series

Страница 1: ...ple actuators and controllers 24 Vac or 28 Vdc power supply Field addable position feedback auxiliary switch module avail able APPLICATION The ML6984 and ML7984 are self contained self adjusting motorized valve actuators that mount directly onto V5011 two way and V5013 three way globe valves providing linear stem operation between 13 mm 1 2 and 25 mm 1 ML6984 is for use with low voltage SPDT Serie...

Страница 2: ... Stem Coupling 1 4 28 UNF thread Stroke Timing Nominal 63 seconds for 3 4 stroke Proportional to stroke length at 24 Vac Closing Force 710 N 160 lbs minimum at 24 Vac Force varies 22 N V 5 lbf volt Performance Specifications Life Expectancy at rated load and power conditions 50 000 full stroke cycles plus 1 000 000 repositions of 10 stem travel or 10 years whichever occurs first Hysteresis 5 Short...

Страница 3: ...r rubber O ring over the valve stem Fig 3 Indicator will self align to the marking on the yoke after complete operating cycle FIG 2 MINIMUM MOUNTING CLEARANCE When Installing This Product 1 Read these instructions carefully Failures to follow them could damage the product or cause a hazardous condition 2 Check ratings given in instructions and on the product to ensure the product is suitable for y...

Страница 4: ...astic cover from the MLx984 by loosening the two captive screws located on the top Drop the Allen Hex type of set screw included in the plastic bag into the top of the shaft hex side up 6 Tighten the set screw to lock valve stem in place Fig 6 using a 1 8 Allen wrench included FIG 4 U BOLT ASSEMBLY NOTE Use U bolt supplied with actuator Do not replace with stainless steel U bolt on chilled water v...

Страница 5: ...4 WITH XL10 ELECTRONIC CONTROLLER For Figures 8A 8B and 8C the following apply 1 2 3 4 5 Power supply provides overload protection and disconnect means Allow up to 0 5 amps for each device Actuators and controller can share same transformer provided that the VA rating of the transformer is not exceeded and proper phasing is observed Do not mix a c and d c power sources Controller can be low voltag...

Страница 6: ... c power sources In ML7984 T5 and W terminals are connected internally Device is compatible with 3 conductor wiring Use configuration DIP switches to select device functions Direct acting function actuator stem moves downwards with signal increases to 10V 20mA or Reverse acting function actuator stem moves upwards with signal increases to 10V 20mA Always turn power off before setting the DIP switc...

Страница 7: ...n DIP switches to select device functions Direct acting function actuator stem moves upwards with signal increase or Reverse acting function actuator stem moves downwards with signal increase Turn power off before setting the DIP switches For common transformer and common controller application please consult the factory For Figure 10A Only Maximum resistance per control circuit of 280 For Figure ...

Страница 8: ...function actuator stem moves upwards with signal increases to 10V 20mA or Reverse acting function actuator stem moves downwards with signal increases to 10V 20mA Turn power off before setting the DIP switches 1 2 3 4 5 8 95C 10939 4 4 5 T6 T5 B R W 3 2 ML7984 T6 T5 B R W 1 L1 L2 OR 28 Vdc 24 Vac T5 T6 3 2 ML7984 3 2 ML7984 T6 T5 B R W R W R W R W ELECTRONIC SERIES 90 W973 T775 H775 W7100 NOTE Pola...

Страница 9: ... the installer may occur 5 DO NOT connect 24 Vac between any ML7984 signal input terminals DEVICE FAILURE WILL RESULT NOTE Caution GENERAL NOTE 1 The ML7984 must be field configured with the DIP switches which are located beside the terminal block See wiring diagrams for details Turn power off before setting the DIP switches 2 There is a 1 5 second delay in actuator response to every signal change...

Страница 10: ...e needed Use Resistor Kit Part 272822 and set DIP switches accordingly See Figures 12 13 TO REPLACE ML684 1 The new ML6984 is a direct replacement for the old ML684A in single actuator or parallel multiple actuators hook up The old and new actuators can be mixed in the same electrical circuit For multiple actuators controlled by a common controller in parallel these actuators must be wired so that...

Страница 11: ...ke sure the valve stem is locked in place with the set screw 3 Connect 24 Vac or 28 Vdc power to T5 and T6 4 Jumper R B The valve stem should move up 5 Jumper R W The valve stem should move down 6 For Floating operation open R connection Valve stem should remain in position 7 Re connect all control wiring 8 Operate the system valve actuator and controller for several cycles to ensure proper instal...

Страница 12: ...ge No or low power supply 1 Check power supply 2 Check callibration cycle 3 Valve stroke length less than 1 2 or greater than 1 1 4 4 Reset device by a momentary disconnect of power at T5 and T6 Check voltage on T5 T6 terminals Change DIP switch setting ML7984 in mA mode with voltage input Signal degradation due to incompatible load impedance Output and ML Input Impedance specifications Galvanic r...