91
31-00559-01
Table 8.16. Torque Characteristics Frame D.
8.4 Ambient Conditions
Table 8.17. Environment.
8.5 Cable Specifications
Table 8.18. Cable lengths and cross-sections for control cables.
Starting torque (Constant torque)
maximum 150% for 60 s
1, 2
Overload Torque (Constant torque)
maximum 150% for 60 s
1, 2
1) Percentage relates to the nominal current of the drive.
2) Once every 10 minutes.
Enclosure Ratings
NEMA1/IP21 (All Frame Sizes)
NEMA12/IP55 (Frame A, B, C)
NEMA12/IP54 (Frame D)
Vibration Test
1.0 g
Max. relative Humidity
5%-93% (IEC 721-3-3; Class 3K3 (non-
condensing) during operation
Aggressive environment (IEC 60068-2-43) H2S
test
class Kd
Ambient temperature
Max 122°F [50°C] (24-hour average maximum
113°F [45°C])
Derating for high ambient temperature, see special conditions in the Design Guide
Minimum ambient temperature during full-scale
operation
32°F [0°C]
Minimum ambient temperature at reduced
performance
14°F [-10°C]
Temperature during storage/transport
-13°-+149/158°F [-25-+65/70°C]
Maximum altitude above sea level without
derating
3,300 ft [1000 m]
Derating for high altitude, see special conditions in the Design Guide
EMC Standards, Emission
EN 61800-3
EMC standards, Immunity
EN 61800-3
Maximum motor cable length, shielded/armored
500 ft [150 m]
Maximum motor cable length, unshielded/unarmored
1,000 ft [300 m]
Maximum cross-section to motor, mains, load sharing, and brake
See Chapter 8.1 Electrical Data
Maximum cross-section to control terminals, flexible/ rigid wire
without cable end sleeves
16 AWG [1.5 mm
2
]
Maximum cross-section to control terminals, flexible wire with
cable end sleeves
18 AWG [1 mm
2
]
Содержание 3G SmartVFD HVFD3D2A0020
Страница 1: ...3G SmartVFD Installation and User Guide ...
Страница 5: ...iv 31 00559 01 ...
Страница 15: ...10 31 00559 01 ...
Страница 19: ...14 31 00559 01 ...
Страница 23: ...18 31 00559 01 ...
Страница 53: ...48 31 00559 01 ...
Страница 83: ...78 31 00559 01 ...
Страница 109: ...103 31 00559 01 ...
Страница 125: ...119 31 00559 01 ...
Страница 126: ......
Страница 127: ... Honeywell 715 Peachtree Street NE Atlanta GA 30308 buildings honeywell com 31 00559 01 08 22 ...