5.2 Applying Power
Apply power to the adjustable frequency drive using the following steps:
Step 1.
Confirm that the input voltage is balanced within 3%. If not, correct
input voltage imbalance before proceeding. Repeat this procedure after
the voltage correction.
Step 2.
Ensure that optional equipment wiring, if present, matches the
installation application.
Step 3.
Ensure that all operator devices are in the OFF position. Panel doors
must be closed or cover mounted.
Step 4.
Apply power to the unit. DO NOT start the adjustable frequency drive now.
Note:
When the status line at the bottom of the LCP reads AUTO REMOTE COASTING or
EXTERNAL INTERLOCK [A60] is displayed, this message indicates that the unit is
ready to operate but is missing an input signal on, for example, terminal 27. See
Chapter 4.8.3 Enabling Motor Operation (Terminal 27) for details.
5.3 Local Control Panel Operation
5.3.1 Local Control Panel
The local control panel (LCP) is the combined display and keypad on the front of
the unit.
The LCP has several user functions:
•
Start, stop, and control speed when in local control
•
Display operational data, status, warnings and cautions
•
Programming adjustable frequency drive functions
•
Manually reset the adjustable frequency drive after a fault when auto-reset is
inactive
UNINTENDED START
When the adjustable frequency drive is connected to AC line power, the motor
may start at any time, causing risk of death, serious injury, equipment, or prop-
erty damage. The motor can start by means of an external switch, a serial bus
command, an input reference signal from the LCP, or after a cleared fault con-
dition.
•
Disconnect the adjustable frequency drive from line power whenever
personal safety considerations make it necessary to avoid unintended motor
start.
•
Press [Off] on the LCP before programming parameters.
•
The adjustable frequency drive, motor, and any driven equipment must be in
operational readiness when the adjustable frequency drive is connected to
AC line power.
Содержание 3G SmartVFD HVFD3D2A0020
Страница 1: ...3G SmartVFD Installation and User Guide ...
Страница 5: ...iv 31 00559 01 ...
Страница 15: ...10 31 00559 01 ...
Страница 19: ...14 31 00559 01 ...
Страница 23: ...18 31 00559 01 ...
Страница 53: ...48 31 00559 01 ...
Страница 83: ...78 31 00559 01 ...
Страница 109: ...103 31 00559 01 ...
Страница 125: ...119 31 00559 01 ...
Страница 126: ......
Страница 127: ... Honeywell 715 Peachtree Street NE Atlanta GA 30308 buildings honeywell com 31 00559 01 08 22 ...