30
31-00559-01
Table 4.2. Terminal Description.
Additional terminals:
•
Two form C relay outputs. Location of the outputs depends on adjustable
frequency drive configuration.
•
Terminals located on built-in optional equipment. See the manual provided with
the equipment option.
Terminal
Parameter
Default Setting
Description
Digital Inputs/Outputs
12, 13
—
+24 V DC
24 V DC supply voltage for digital inputs and external
transducers.
Maximum output current 200 mA for all 24 V loads.
18
5-10
[8] Start
Digital inputs.
19
5-11
[0] No operation
32
5-14
[0] No operation
33
5-15
[0] No operation
27
5-12
[2] Coast
inverse
For digital input or output. Default setting is input.
29
5-13
[14] JOG
20
—
Common for digital inputs and 0 V potential for 24 V
supply.
Analog Inputs/Outputs
39
—
Common for analog output.
42
6-50
Speed 0 - High
Limit
Programmable analog output. 0–20 mA or 4–20 mA at
a maximum of 500
Ω
50
—
+10 V DC
10 V DC analog supply voltage for potentiometer or
thermistor. 15 mA maximum
53
6-1
Reference
Analog input. For voltage or current. Switches A53 and
A54 select mA or V.
54
6-2
Feedback
55
—
Common for analog input.
Serial Communication
61
—
Integrated RC filter for cable shield. ONLY for
connecting the shield in the event of EMC problems.
68 (+)
8-3
RS-485 Interface. A control card switch is provided for
termination resistance.
69 (-)
8-3
Relays
01, 02, 03
5-40 [0]
[9] Alarm
Form C relay output. For AC or DC voltage and resistive
or inductive loads.
04, 05, 06
5-40 [1]
[5] Running
Содержание 3G SmartVFD HVFD3D2A0020
Страница 1: ...3G SmartVFD Installation and User Guide ...
Страница 5: ...iv 31 00559 01 ...
Страница 15: ...10 31 00559 01 ...
Страница 19: ...14 31 00559 01 ...
Страница 23: ...18 31 00559 01 ...
Страница 53: ...48 31 00559 01 ...
Страница 83: ...78 31 00559 01 ...
Страница 109: ...103 31 00559 01 ...
Страница 125: ...119 31 00559 01 ...
Страница 126: ......
Страница 127: ... Honeywell 715 Peachtree Street NE Atlanta GA 30308 buildings honeywell com 31 00559 01 08 22 ...