87
31-00559-01
Table 8.10. Line Power Supply 3x525–600 V AC - Normal overload 110% for 1 minute,
15 to 40 HP.
1) Efficiency measured at nominal current. For energy efficiency class see Chapter 8.4 Ambient
Conditions.
2) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the
default setting, the power losses may increase. LCP and typical control card power consumptions are in-
cluded.
Type Designation, HVFD3D…
3D0150
3D0200
3D0250
3D0300
3D0400
Typical Shaft Output [HP]
15
20
25
30
40
Typical Shaft Output [kW]
11
15
18.5
22
30
IP21/NEMA 1
B1
B1
B1
B2
B2
IP55/NEMA 12
B1
B1
B1
B2
B2
Output Current
Continuous (3 x 525–550 V) [A]
19
23
28
36
43
Intermittent (3 x 525–550 V) [A]
21
25
31
40
47
Continuous (3x525–600 V) [A]
18
22
27
34
41
Intermittent (3x525–600 V) [A]
20
24
30
37
45
Continuous kVA (525 V AC) [kVA]
18.1
21.9
26.7
34.3
41
Continuous kVA (575 V AC) [kVA]
17.9
21.9
26.9
33.9
40.8
Max. Input Current
Continuous (3x525–600 V) [A]
17.2
20.9
25.4
32.7
39
Intermittent (3x525–600 V) [A]
19
23
28
36
43
Additional Specifications
Estimated power loss at rated max.
load [W]4)
300
400
475
525
700
IP21, IP55 max. cable cross- section
(line power, brake and load sharing)
[AWG/(mm
2
)]
7 (10)
2 (35)
IP21, IP55 max. cable cross-section
(motor) [AWG/(mm
2
)]
7 (10)
2 (35)
Efficiency
3
0.98
0.98
0.98
0.98
0.98
Содержание 3G SmartVFD HVFD3D2A0020
Страница 1: ...3G SmartVFD Installation and User Guide ...
Страница 5: ...iv 31 00559 01 ...
Страница 15: ...10 31 00559 01 ...
Страница 19: ...14 31 00559 01 ...
Страница 23: ...18 31 00559 01 ...
Страница 53: ...48 31 00559 01 ...
Страница 83: ...78 31 00559 01 ...
Страница 109: ...103 31 00559 01 ...
Страница 125: ...119 31 00559 01 ...
Страница 126: ......
Страница 127: ... Honeywell 715 Peachtree Street NE Atlanta GA 30308 buildings honeywell com 31 00559 01 08 22 ...