IMMERSION WELLS AND COMPRESSION FITTINGS

9

68-0040—04

WARNING

Electrical Shock Hazard or Equipment Damage 

Hazard.

Can cause sever injury, death or short equipment 

circuitry.

Disconnect all power supplies before installation.

Most equipment manufacturers provide a tapping for 

temperature controller sensing element insertion. The tapping 

should be located to measure average system temperature.

IMPORTANT

Always install the sensing element away from hot or 

cold water inlets, steam coils, and locations where the 

well pressure rating will be exceeded.

1.

Turn off the power.

2.

If the system is filled, drain it to a point below the boiler 

tapping or sensing element location.

3.

If no tapping is provided, prepare one, properly threaded, 

at the desired location.

Immersion Well Mounting

Instructions for mounting the well in the tapping and using the 

capillary mounting clamp or spring clip in remote bulb 

applications follow. Consult the appropriate Aquastat® 

Controller instructions for mounting the controller on the well in 

direct insertion applications. Direct insertion applications 

usually require using wells with a mounting flange on the spud.

1.

Coat threads with a moderate amount of pipe dope, leav-

ing two end threads bare. See Fig. 4.

NOTE: Teflon™ tape can also be used.

2.

Screw the immersion well into the tapping and tighten 

securely.

Fig. 4. Proper application of pipe dope.

Insert Sensing Bulb in Well

For good temperature response, the immersion well must fit 

the sensing element or bulb tightly and rest against the bottom 

of the well.

NOTE: If necessary, bend the tubing to hold the bulb against 

the bottom of the well.

IMPORTANT

Any bends made in the piping must be gradual to pre-

vent breaks in the tubing and subsequent loss of fill.

For faster heat transfer, use heat-conductive compound to fill 

the space between the bulb and the well. A tube of 

heat-conductive compound ships with Honeywell 

TRADELINE® Aquastat Controllers. The compound is also 

available as an accessory. See Table 5. Use the following 

procedure when installing the compound:

1.

Fill the well with compound.

2.

Coat the bulb generously before inserting it into the well.

3.

Move the bulb up and down inside the well to ensure 

even distribution of compound.

Securing Bulb with Mounting Clamp

Use the 121371 Mounting Clamp 

only

 on wells with a mounting 

flange on the spud end.

1.

Loosen the draw nut and spread the jaws of the clamp 

with a screwdriver. See Fig. 5.

2.

Slide the clamp jaws over the spud mounting flange 

(point A in Fig. 5).

3.

Adjust the tubing to fit through the mounting clamp 

groove (point B in Fig. 5).

IMPORTANT

When tightening the draw nut, be careful not to 

damage the capillary.

4.

Tighten the draw nut so that the retainer clamp attaches 

firmly to the well spud and holds the tubing securely in 

place.

Fig. 5. Fastening bulb in well using mounting clamp.

Securing Bulb with Spring Clip

The spring clip can be used with any well with the appropriately 

size spud. Wells without a mounting flange on the spud require 

a spring clip.

NOTE: The spring clip does not hold the capillary as securely 

as does the mounting clamp. See Table 5 for spring 

clip part numbers.

1.

Slide the clip over the capillary with the prongs facing the 

well.

2.

Push the clip as far as possible into the spud. See Fig. 6.

NOTE: Make sure the bulb remains bottomed in the well.

APPLY A MODERATE AMOUNT 
OF PIPE COMPOUND (LEAVE 
TWO END THREADS BARE).

M17262

M8777

WELL

BULB

SPUD

MOUNTING
CLAMP

A

DRAW 
NUT

TUBING

B

MOUNTING CLAMP

SCREWDRIVER

SPREAD JAWS
TO FIT OVER
RIDGE ON 
WELL SPUD

JAWS

Содержание 104484A

Страница 1: ... steel mild steel or Monel Element holders support the capillary and bulb or an averaging element in duct applications Bulb shields protect the sensing bulb from sun and weather with the bulb installed outdoors Accessories including mounting clips heat conductive compound waste nuts a pipe strap and a well adapter are available for mounting sensing bulbs in various applications Immersion wells all...

Страница 2: ... for copper See Table 2 for stainless steel mild steel and Monel Compression Fittings Allow bulb insertion directly into the controlled medium with boiler draining Can also be used to provide positive seal in duct applications Available in brass and stainless steel See Table 3 Element Holders Support bulb and capillary or averaging element in a duct See Table 4 Dimensions See Tables 1 2 3 and 4 an...

Страница 3: ...MOUNTING FLANGE MOUNTING FLANGE MOUNTING CLAMP WELL SPUD FITS 1 2 OR 3 4 14 NPT TAPPED HOLE FITS 1 2 OR 3 4 14 NPT TAPPED HOLE FITS 1 2 OR 3 4 14 NPT TAPPED HOLE FITS 1 2 OR 3 4 14 NPT TAPPED HOLE 1 8 1 2 in OF THREADS MAY EXTEND INTO CONTROLLED MEDIUM 1 8 1 2 in OF THREADS MAY EXTEND INTO CONTROLLED MEDIUM WELL SHELL M17259A SET SCREW FITS 1 2 OR 3 4 14 NPT TAPPED HOLE FITS 1 2 OR 3 4 14 NPT TAPP...

Страница 4: ...nting Clamp 121371B 123870A 3 5 64 121371 Mounting Clamp 121371M 121371 Mounting Clamp plastic sleeve 123171N 123871A Plastic sleeve on well tube 123871B 4 1 2 122555D Plastic sleeve on well tube 122555A 3 1 2 1 1 2 5 64 121371 Mounting Clamp 121371Q 2 1 4 138134B 4 1 2 Plastic sleeve on well tube 122555B 122555C 3 8 5 8 3 2 1 4 Plastic sleeve on well tube 138134E 4 1 2 122555E 1 2 4 1 4 1 1 2 1 8...

Страница 5: ...8 5 8 in 2 3 4 in x 1 3 4 in Supports capillary and bulb in duct mounting screws not included 2 3 4 in x 3 in 14 in 3 1 4 in x 3 1 4 in Holds 1 or 2 elements in 0 F to 100 F air grommet holds one 5 64 in and one 1 8 in diameter capillary helps reduce airflow through opening in duct Averaging element holders Mounting clip use with grommet mounting screws not included one required per clip Use with ...

Страница 6: ... Holds capillary in place on 1122620AA 112639AB Immersion Wells 1 2 in well spud 5 64 capillary 112721 112720 1 2 in well spud 1 8 capillary 3 4 in well spud 1 8 capillary Heat conductive compound Improves heat conduction in well applications where bulb does not fit tightly 4 oz 118 ml Single application tube 1 2 oz Well Adapter Adapts well with setscrew on spud for use with direct insertion bulb ...

Страница 7: ...l mild steel and Monel wells are also available for applications requiring higher maximum temperature and pressure ratings or greater corrosion resistance Some copper wells are available with a plastic sleeve over the tube to reduce electrolytic and corrosive activity Well Sizing Major factors in selecting well size are size of the boiler tapping bulb diameter insulation depth insertion length Imm...

Страница 8: ...ng material and the packing nut and externally threaded to fit standard boiler tappings The washers and packing ring are sized to fit a particular capillary diameter Capillary compression fittings are used to replace an immersion well when the sensing bulb of a remote bulb controller requires direct insertion into the controlled medium The fitting seals around the capillary However compression fit...

Страница 9: ... must be gradual to pre vent breaks in the tubing and subsequent loss of fill For faster heat transfer use heat conductive compound to fill the space between the bulb and the well A tube of heat conductive compound ships with Honeywell TRADELINE Aquastat Controllers The compound is also available as an accessory See Table 5 Use the following procedure when installing the compound 1 Fill the well w...

Страница 10: ...re air at representative temperatures can circulate around it In a plenum application locate the element far enough from the combustion chamber to avoid the effect of direct radiation Bulb Holders 1 Cut a hole large enough to admit the bulb and holder in the duct or plenum at the mounting location 2 Drill holes for the bulb holder mounting screws 3 Mount the bulb and capillary on the holder See Fi...

Страница 11: ...et inserted in a hole in the duct wall For ducts with limited access the 7640HX Averaging Element Mounting Kit allows mounting the element through a single hole in the side of the duct This kit requires a length of 1 2 in EMT conduit See Fig 15 Fig 13 Mounting averaging element with perforated strap iron Fig 14 Mounting averaging element with 314439 Mounting Clips Fig 15 Mounting averaging element...

Страница 12: ... use either the 105900 Pipe Strap or metal hose clamps The pipe strap fits pipe up to 3 4 in OD External mounting of the sensor produces a slight offset in the temperature control point Typically the control temperature increases as much as 5 F 2 8 C with a bare sensor strapped to the discharge pipe Applying insulation around the sensor and pipe decreases the offset Insulation must be used if larg...

Страница 13: ...ving the system through one complete cycle CROSS REFERENCE Some series 121371 Wells are also available without the mounting clamp These pairs are listed together in Table 1 and in Table 7for your convenience The cross reference in Table 8 lists wells and fittings no longer available and suggests functional replacements Table 7 Wells With and Without Mounting Clamp 121371 Part Number With Clamp Par...

Страница 14: ...iameter bulb None 122555G Immersion well Copper 3 4 14 NPT 4 1 2 in insulation 5 in insertion dual diameter bulb None 123870E Immersion well Copper 3 4 14 NPT 1 1 2 in insulation 3 in insertion includes plastic sleeve dual diameter capsule 138134E 2 1 4 in insulation 123871D Immersion well Copper 3 4 14 NPT 3 in insulation 3 in insertion includes plastic sleeve dual diameter well 138134E 123871E I...

Страница 15: ...IMMERSION WELLS AND COMPRESSION FITTINGS 15 68 0040 04 ...

Страница 16: ... Registered Trademark 2008 Honeywell International Inc 68 0040 04 M S Rev 07 08 By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or r...

Отзывы: