IMMERSION WELLS AND COMPRESSION FITTINGS

68-0040—04

12

Bulb Shields

A bulb mounted outdoors requires protection of a bulb shield.

1.

Expose the bulb to representative air temperature but 

not direct sunlight.

2.

Mount it high enough so:

a. Accumulated snow, leaves or other debris can-

not obstruct air circulation around it.

b. Children cannot reach it.

c. Avoid vents from the building.

3.

Drill a 3/4 in. (19 mm) hole in the outside wall.

4.

Bring the sensing bulb through the hole.

5.

Mount the bulb in the bulb shield. See Fig. 16.

6.

If the seal-off tube extends outside the shield, bend it 

under the shield.

7.

Hold the shield over the mounting location and form a 

small-radius bend in the tubing.

8.

Place the split plug (provided with 34886A; or order 

107323A Split Plug separately) around the tubing and 

move the bulb and shield into mounting position as a sin-

gle unit.

9.

Push the split plug into the hole until it is wedged 

securely in place.

10.

Fasten the shield on the wall with screws (provided with 

34886A).

11.

If the tubing is properly shaped and the split plug 

installed as directed, the shield covers the split plug and 

conceals the hole in the wall.

Fig. 16. Mounting bulb in bulb shield.

Strap-On Mounting

Occasionally, applications require the sensing bulb to be 

strapped to the outside of a pipe. For these applications, use 

either the 105900 Pipe Strap or metal hose clamps. The pipe 

strap fits pipe up to 3/4 in. OD.

External mounting of the sensor produces a slight offset in the 

temperature control point. Typically, the control temperature 

increases as much as 5°F (2.8°C) with a bare sensor strapped 

to the discharge pipe. Applying insulation around the sensor 

and pipe decreases the offset. Insulation must be used if large 

fluctuations in ambient temperature occur near the pipe.

Mount the bulb on the pipe as follows:

CAUTION

Significant Calibration Shift Hazard.

Overtightening clamps distorts bulb calibration.

Do not overtighten hose clamps.

1.

Secure the bulb to the pipe with a 105900 Pipe Strap or 

metal hose clamps. See Fig. 17 and 18.

2.

If necessary, cover the bulb and pipe with foam rubber 

insulation that extends at least 6 in. (152 mm) beyond 

both ends of the bulb. See Fig. 19.

IMPORTANT

Do not allow the duct tape to come into contact with 

the pipe.

3.

Secure foam rubber with duct tape.

Fig. 17. Mounting bulb to pipe with pipe strap.

NOTE: When using a pipe strap, the maximum pipe OD is 3/4 

in.

Fig. 18. Mounting bulb to pipe with metal hose clamps.

Fig. 19. Covering bulb and pipe with foam rubber 

insulation.

M17272A

OUTDOOR

SENSING

BULB

EXTENSION

TUBE

BULB SHIELD

CAPILLARY

TUBING

3/4 IN. (19 mm)

HOLE IN WALL

PLUG HOLE WITH

ACCEPTABLE MATERIAL

BULB

T-CLAMP

CAPILLARY

TUBING

SUPPLY WATER PIPE

M8836

CAPILLARY TUBE

METAL HOSE CLAMPS

M17267

M17268 

FOAM RUBBER WRAP (EXTEND 

6 in. (152 mm) BEYOND ENDS OF BULB)

CAPILLARY

TUBE

PIPE

DUCT

TAPE

Содержание 104484A

Страница 1: ... steel mild steel or Monel Element holders support the capillary and bulb or an averaging element in duct applications Bulb shields protect the sensing bulb from sun and weather with the bulb installed outdoors Accessories including mounting clips heat conductive compound waste nuts a pipe strap and a well adapter are available for mounting sensing bulbs in various applications Immersion wells all...

Страница 2: ... for copper See Table 2 for stainless steel mild steel and Monel Compression Fittings Allow bulb insertion directly into the controlled medium with boiler draining Can also be used to provide positive seal in duct applications Available in brass and stainless steel See Table 3 Element Holders Support bulb and capillary or averaging element in a duct See Table 4 Dimensions See Tables 1 2 3 and 4 an...

Страница 3: ...MOUNTING FLANGE MOUNTING FLANGE MOUNTING CLAMP WELL SPUD FITS 1 2 OR 3 4 14 NPT TAPPED HOLE FITS 1 2 OR 3 4 14 NPT TAPPED HOLE FITS 1 2 OR 3 4 14 NPT TAPPED HOLE FITS 1 2 OR 3 4 14 NPT TAPPED HOLE 1 8 1 2 in OF THREADS MAY EXTEND INTO CONTROLLED MEDIUM 1 8 1 2 in OF THREADS MAY EXTEND INTO CONTROLLED MEDIUM WELL SHELL M17259A SET SCREW FITS 1 2 OR 3 4 14 NPT TAPPED HOLE FITS 1 2 OR 3 4 14 NPT TAPP...

Страница 4: ...nting Clamp 121371B 123870A 3 5 64 121371 Mounting Clamp 121371M 121371 Mounting Clamp plastic sleeve 123171N 123871A Plastic sleeve on well tube 123871B 4 1 2 122555D Plastic sleeve on well tube 122555A 3 1 2 1 1 2 5 64 121371 Mounting Clamp 121371Q 2 1 4 138134B 4 1 2 Plastic sleeve on well tube 122555B 122555C 3 8 5 8 3 2 1 4 Plastic sleeve on well tube 138134E 4 1 2 122555E 1 2 4 1 4 1 1 2 1 8...

Страница 5: ...8 5 8 in 2 3 4 in x 1 3 4 in Supports capillary and bulb in duct mounting screws not included 2 3 4 in x 3 in 14 in 3 1 4 in x 3 1 4 in Holds 1 or 2 elements in 0 F to 100 F air grommet holds one 5 64 in and one 1 8 in diameter capillary helps reduce airflow through opening in duct Averaging element holders Mounting clip use with grommet mounting screws not included one required per clip Use with ...

Страница 6: ... Holds capillary in place on 1122620AA 112639AB Immersion Wells 1 2 in well spud 5 64 capillary 112721 112720 1 2 in well spud 1 8 capillary 3 4 in well spud 1 8 capillary Heat conductive compound Improves heat conduction in well applications where bulb does not fit tightly 4 oz 118 ml Single application tube 1 2 oz Well Adapter Adapts well with setscrew on spud for use with direct insertion bulb ...

Страница 7: ...l mild steel and Monel wells are also available for applications requiring higher maximum temperature and pressure ratings or greater corrosion resistance Some copper wells are available with a plastic sleeve over the tube to reduce electrolytic and corrosive activity Well Sizing Major factors in selecting well size are size of the boiler tapping bulb diameter insulation depth insertion length Imm...

Страница 8: ...ng material and the packing nut and externally threaded to fit standard boiler tappings The washers and packing ring are sized to fit a particular capillary diameter Capillary compression fittings are used to replace an immersion well when the sensing bulb of a remote bulb controller requires direct insertion into the controlled medium The fitting seals around the capillary However compression fit...

Страница 9: ... must be gradual to pre vent breaks in the tubing and subsequent loss of fill For faster heat transfer use heat conductive compound to fill the space between the bulb and the well A tube of heat conductive compound ships with Honeywell TRADELINE Aquastat Controllers The compound is also available as an accessory See Table 5 Use the following procedure when installing the compound 1 Fill the well w...

Страница 10: ...re air at representative temperatures can circulate around it In a plenum application locate the element far enough from the combustion chamber to avoid the effect of direct radiation Bulb Holders 1 Cut a hole large enough to admit the bulb and holder in the duct or plenum at the mounting location 2 Drill holes for the bulb holder mounting screws 3 Mount the bulb and capillary on the holder See Fi...

Страница 11: ...et inserted in a hole in the duct wall For ducts with limited access the 7640HX Averaging Element Mounting Kit allows mounting the element through a single hole in the side of the duct This kit requires a length of 1 2 in EMT conduit See Fig 15 Fig 13 Mounting averaging element with perforated strap iron Fig 14 Mounting averaging element with 314439 Mounting Clips Fig 15 Mounting averaging element...

Страница 12: ... use either the 105900 Pipe Strap or metal hose clamps The pipe strap fits pipe up to 3 4 in OD External mounting of the sensor produces a slight offset in the temperature control point Typically the control temperature increases as much as 5 F 2 8 C with a bare sensor strapped to the discharge pipe Applying insulation around the sensor and pipe decreases the offset Insulation must be used if larg...

Страница 13: ...ving the system through one complete cycle CROSS REFERENCE Some series 121371 Wells are also available without the mounting clamp These pairs are listed together in Table 1 and in Table 7for your convenience The cross reference in Table 8 lists wells and fittings no longer available and suggests functional replacements Table 7 Wells With and Without Mounting Clamp 121371 Part Number With Clamp Par...

Страница 14: ...iameter bulb None 122555G Immersion well Copper 3 4 14 NPT 4 1 2 in insulation 5 in insertion dual diameter bulb None 123870E Immersion well Copper 3 4 14 NPT 1 1 2 in insulation 3 in insertion includes plastic sleeve dual diameter capsule 138134E 2 1 4 in insulation 123871D Immersion well Copper 3 4 14 NPT 3 in insulation 3 in insertion includes plastic sleeve dual diameter well 138134E 123871E I...

Страница 15: ...IMMERSION WELLS AND COMPRESSION FITTINGS 15 68 0040 04 ...

Страница 16: ... Registered Trademark 2008 Honeywell International Inc 68 0040 04 M S Rev 07 08 By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or r...

Отзывы: