Hazard information
The load current circuits have to be secured by a
cable protection switch in accordance with
EN60898-1 (tripping characteristic B or C, max.
10 A rated current, min. 6 kA interrupting rating,
energy limiting class 3).
For secure operation, the device has to be installed in
a power distribution panel according to VDE 0603,
DIN 43871 (low-voltage sub-distribution board), DIN
18015-x. The installation must be carried out on a
mounting rail (DIN rail) according to EN 60715. Instal-
lation and wiring have to be performed according to
VDE 0100 (VDE 0100-410, VDE 0100-510 etc.).
Please consider the technical connection require-
ments (TAB) of your energy supplier.
Before installation and connection of the device,
mains voltage must be disconnected and live
parts in the surrounding must be covered.
The device has not been designed to support
safety disconnection.
Only shutters and blinds with limit switches (me-
chanical or electronic) should be used. Before
putting the actuator into operation, check that
the limit switches on the connected motors have
been adjusted correctly.