EngliSH | 27
BA V2.0 01052020
Both the station status and station data sets can be stored
on the mobile device.
Faults and events
An event list and a fault message list are saved in the con-
troller. Both lists are retained in the event of a power fail-
ure. All events, whether marked as having „occurred“ or
„retreated“, are recorded in the event list, along with their
respective date and time. For the sake of clarity, faults in
the fault message list are only shown with „occurred“.
An established connection to the controller is shown in
HOMApp by a green bar. If the connection is interrupted,
the display changes from green to red.
7.3.2. Configure PCM (password required)
- Checking data and transferring it to the PCM -
When this menu item is selected, the app searches for a
nearby PCM controller. Please make sure that the Blue-
tooth LED on the controller is lit up. Establish a connection
with the chosen PCM.
Now all the necessary settings for the controller can be
made. You can access complete, predefined data sets,
and change and save them as required. The storage loca-
tion can be the mobile device or PCM.
The entire configuration can be transferred to the con-
troller from the menu.
When transferring data, please note the following points
with regard to the controller:
•
If the level measurement is changed, the control pro-
gram is restarted. The green „Unlock“ LED goes out
briefly and then lights up again. You need to recon-
nect to the app.
•
If the name of the pump station is also changed, a
further restart takes place. In this case, you will also
need to log into the app again.
•
The upload process is finished when the controller
acknowledges completion with a series of tones.
The menu contains the sections
Base configuration
and
Station parameters
.
Base configuration
This contains basic settings and options, such as:
•
Transfer data to the PCM
•
Load, change and save an existing data set from the
list of data sets
•
Define long texts for data sets
•
Select single or double control
•
Measuring system
Select dynamic pressure measurement
Select float switch
Select 4-20 mA
•
Select overload relay – yes/no
•
230 V output – define function
No function
Alarm flashing in case of collective fault (pump 1
faulty, pump 2 faulty or high water level)
230 V power output (continuous voltage)
•
Compressor cycles
Содержание PCM Series
Страница 15: ...DEUTSCH 15 BA V2 0 01052020 11 Anhang ...
Страница 31: ...EngliSH 31 BA V2 0 01052020 11 Appendix ...
Страница 34: ......