HSK_operating_manual_English_Ver3.doc
HOMA Pump Technology
-
14
-
This message is not important for the user and it indicates only the internal configuration for service
purposes. Subsequently the copyright message with the SW-version number is indicated for approx.
1sec. After this, the HSK initiates the start delay time.
6 System
menus
6.1
Level measurement
6.2
In the menu "Level measurement", the level measurement method, setpoints, high water levels
as well as the minimum pressure (level measurement with bubbler system) are specified.
Cut-Out Level
Pump 1: 0030cm
Cut-Out Level
Pump 2: 0031cm
Cut-In Level
Pump 1: 0040cm
Cut-In Level
Pump 2: 0061cm
Alarm Level
0091cm
Level Messurement
4...20mA 0250cm
Automatic
Zero Adjustment
Filter (0-9999)
0000
Minimum Pressure
0005cm
... back to
Main Menu
6.1.1 Level measurement setting
In this menu, the level measurement method is determined. After pressing the
OK
-key, the level
measurement method can be selected by means of the
▲
- or
▼
-key. Following possibilities are
available:
•
level measurement 4… 20mA interface through level sensor, measuring range adjustable from
0100cm (1meter WC up to 1000cm (10 meters WC)
•
internal impact pressure sensor (measuring range 0 … 200 cm WC
•
1 x float switch
•
2 x float switches
•
3 x float switches (only possible with
HSK25
in dual pump operation)
After the measuring method has been selected, it must be confirmed with the
OK
-key
If a 4-20mA level sensor has been selected as measurement method, then after pressing the
OK
-key,
the measuring range of the connected sensor must be additionally entered in cm.