Theory of Operation
7
HP-306
3.
THEORY OF OPERATION
The HIT-2A consists of six functional blocks. These functional blocks
are the User Interface, Preamplifier, Microcontroller, Loop Driver,
Pulse and Alarm Output, and Communications Interface.
3-1
Functional Blocks
3-1-1
User Interface
The User Interface consists of a custom LCD display with 4 push
buttons; OK, P, > (right arrow), and ^ (up arrow) and an optional
external reset. Using the buttons and the displayed information,
the user can enter setup parameters (rate units, pulses per unit of
flow, etc.) as well as setup information for the pulse output and 4-
20mA output. The optional external reset maybe used to reset the
accumulated total to zero and clear the displayed accumulated
total.
3-1-2
Preamplifier
The Preamplifier accepts the input from the flowmeter. The
Preamplifier applies amplification, low-pass filtering, and wave-
shaping to the input signal. The wave shaping function converts
the signal into a square-wave before sending it to the
Microcontroller.
3-1-3
Microcontroller
The Microcontroller accepts the square-wave output of the
preamplifier and performs all of the calculations that are required
to control the Loop Driver. After measuring the frequency of the
Flowmeter Input
Microcontroller
Loop Driver
4-20 mA
Pulse Output
Communications
Interface
User
Interface
RS232
Preamp
Opto-isolated
Outputs
Alarm Output
IRDA
Содержание HIT-2A
Страница 2: ......
Страница 6: ...HP 306...
Страница 10: ...Introduction 2B HP 306 This page intentionally left blank...
Страница 14: ...Specification 6 HP 306 This page intentionally left blank...
Страница 18: ...Theory of Operation 10 HP 306 This page intentionally left blank...
Страница 20: ...Installation 12 HP 306 TTL Redi Pulse Pick up with DC Power Reset Input Heater Option...
Страница 26: ...Installation 18 HP 306 This page intentionally left blank...
Страница 34: ...Operation and Maintenance 26 HP 306 This page intentionally left blank...