NSW
02 9644 7144
QLD
07 3252 5366
VIC
03 9544 2211
WA
08 9349 2972
FIREbeam Xtra User Manual
2-3-0-2700/ISS2/21.OCT19
13
CAUTION
: This process should take up to 10 Minutes, if the beam does not complete after
this time then look at the X and Y axis to check it has not deviated off the reflector onto an
obstruction. The X and Y figures should be below 1.50 on each axis and would normally be
below 0.90.
If this is not the case, you may need to start the Manual Alignment process again to return
both beam axis to 0.00 and identify and remove the obstruction.
Step 5 - Testing
The FIREbeam Xtra should now be tested for Fire and Fault.
Note: The beam must be tested at the reflector end and not at the beam head. This is to
confirm it is looking at the reflector and completes the commissioning process.
FAULT
- Cover the reflector within 1 second with a non-reflective
card to simulate a fault such as a fork-lift truck breaking the path of
the beam. After 10 Seconds the beam should register FAULT and
the Amber light will flash.
FIRE
- Cover the reflector slowly up to 70% with a non-reflective card
to simulate a fire such as smoke entering the path of the beam.
After 10 Seconds the beam should register FIRE and the Red light
will flash.
Once you have successfully completed both tests your FIREbeam Xtra is commissioned.
You can now fine tune your beam to suit the environment if needed. Look through the
following menus to see adjustments that can be made.