FIREbeam Xtra User Manual
14
2-3-0-2700/ISS2/21.OCT19
Screen and Menu Systems
Home Screen
NORMAL
This is the screen you would normally see when the beam is
commissioned.
FIRE
The air quality level has fallen below the fire threshold setting.
If alarm is set to latching and you need to reset from fire press enter to see
this screen and press enter again to reset and return to the normal screen.
This can also be reset by dropping the power to the beam for 5 seconds. If
set to auto reset, it will reset to normal automatically. See the menu
system on the following pages on how to change between auto and
latching if required.
FAULT
The beam path has been fully blocked within 1 second (used when fault
testing in commissioning.
ERROR
No communication with the controller. This could be that the flying lead is
not connected, or that the head is not connected to the controller. This can
be checked by reading the resistance across the black and grey terminals,
if connected it should read 110 ohms, if not connected at one end this will
read 220 ohms.
ALIGN
This screen will appear when the beam is performing a self-alignment,
normally because of building movement.
DIRT
COMP
This is due to the compensation for dirt build up reaching its maximum -
FAULT or FIRE LED may be flashing.