2.3 Step 3 - Mounting the Controller
Important mount the controller at eye level and ensure easy access.
Screw in through holes
provided outside of the rubber
seal. Wire to head using colour
coded terminals.
If this connection is not made
ERROR will appear on the
controller, this connection can
be checked by reading the
resistance across the black and
grey terminals, they will read
110 ohm if OK or 220 ohm if
not connected properly.
2.4 Wiring Configuration
The output current will need to be set at 22mA. The output will also need to be programmed so that it is powered in
its normal state. On a control panel reset the output will need to change state for a minimum period of 5 seconds.
NOTE: You should consult the relevant control panel documentation on how to program this functionality.