4 Technical 

Specifications 

 

Electrical Specifications 

Supply Voltage 

17 to 41 Vd.c. 

Supply Current 

3.5mA (constant current) in all operational states 

Constant Current 

17mA (constant current) in fast commissioning 

Environmental Specifications 

Temperature 

-10°C to +55°C 

Humidity 

10 to 95% RH Non-condensing 

Ingress Protection Index 

IP65 when suitably mounted and terminated 

Mechanical Specifications 

Beam Head 

180mmH x 155mmW x137mmD, Weight 1.1Kg 

Controller 

185mmH x 120mmW x 62mmD, Weight 0.55g 

40KIT80 Mid-Range Reflector 

293mmH x293mmW x 5mmD, Weight 0.8Kg 

80KIT100 Long Range Reflector 

394mmH x 394mmW x 5mmD, Weight 1.8Kg 

Adapter (mounts the Beam Head onto unistrut) 

270mmH x 250mmW x 5mmD, Weight 0.6g 

Optical Specifications 

Optical Wavelength 

870nm 

Maximum Angular Alignment 

±5° 

Maximum Angular Misalignment  

Beam Head ±0.3°, Reflector ±2° (static not auto-aligning) 

Operational Specifications 

Protection 
Range 

ESP FIREBEAM 

Standard Product 5 to 40 metres 

40KIT80 

Mid-Range Reflector Kit 40 to 80 metres 

80KIT100 

Long Range Reflector Kit 80 to 100 metres 

Alarm Sensitivity Levels 

25%(1.25dB) to 50%(3dB) in 1%(0.05dB) increments (default 35% (1.87dB)) 

Alarm Condition 

Obscuration drops to below pre-defined sensitivity level.  Time to Alarm Condition 
adjustable 2 to 30 seconds in 1 second increments (default 10 seconds) 

Alarm Indication 

Controller Status – FIRE, Controller Red Flashing LED, Head Red Flashing LED, 
Alarm Relay Change Over (CO) Contact Rating 2A @ 30 VDC 

Test/Reset Features 

Beam test function by controller.  Alarm latching/auto-reset selectable (default 
auto-reset).  Alarm reset in latching mode by controller reset function, removing 
power for >5 seconds, apply 12 to 24 VDC to reset connections in Beam Head. 

Fault Sensitivity Level 

90% 

Fault Condition 

Obscuration drops to below the fault sensitivity level within 1 second Power Down 
or Supply Voltage < 9 VDC.  Commissioning modes, Pre-Alignment and Auto 
Alignment.  Beam turned off during Beam Maintenance.  Time to Fault Condition 
adjustable, 2 to 60 seconds in 1 second increments (default 10 seconds) 

Fault Indication 

Controller Status – FAULT, Controller Yellow Flashing LED 1 Second, Head 
Yellow Flashing LED 1 Second, Fault Relay Change Over (CO) Contact Rating 
2A @ 30 VDC 

Normal Condition 
 

Obscuration level is above the Alarm sensitivity level, Controller Status – 
NORMAL, Controller Green Flashing LED, Programmable on/off, Head Green 
Flashing LED Programmable on/off 

Auto-align/Beam 
Contamination Compensation 

Auto-align during normal operation if obscuration drops below 90% for the 
duration of the align time set (doesn’t effect normal operating mode) 
Beam Contamination Compensation 4 hour monitoring. Compensation data 
available at the controller 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание ESP FIREbeam

Страница 1: ...esp FIREbeam INSTALLATION MANUAL www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...www acornfiresecurity com www acornfiresecurity com...

Страница 3: ...2 Step 2 Programming the Analogue Address 6 2 3 Step 3 Mounting the Controller 7 2 4 Wiring Configuration 7 2 5 Step 4 Commissioning 8 2 5 1 Stage One Language and Commissioning Speed 8 2 5 2 Stage T...

Страница 4: ...ESP FIREbeam comes boxed with the head unit low level controller one reflector 3mm allen key and quick start installation guide this should be used for distances over 5m and up to 40m 1 1 2 40 to 80 m...

Страница 5: ...40m from the floor The maximum protected area either side of the beam can be extended by 1 for every degree of roof pitch see the example below NOTE Careful design consideration should be made when p...

Страница 6: ...the front edge of the box Wire to low level controller using bottom colour coded terminals Screw in through holes provided outside of the rubber seal 2 2 Step 2 Programming the Analogue Address The F...

Страница 7: ...this connection can be checked by reading the resistance across the black and grey terminals they will read 110 ohm if OK or 220 ohm if not connected properly 2 4 Wiring Configuration The output curre...

Страница 8: ...in normal mode the system uses 3 5mA in fast mode it uses 17mA if you are commissioning more than one beam at a time and the system cannot support the extra draw it may be necessary to use normal mod...

Страница 9: ...ng noticeably less read on below These figures are approximate but if you are receiving noticeably less than these figures you may be receiving a reflection from an object nearby and not the far wall...

Страница 10: ...higher the AQ the quicker it will auto align This is done by manually moving the x and y motors to obtain a received signal from the reflector In the example below we can see that the reflector is bel...

Страница 11: ...low 100 Now proceed to Step 4 Testing the final stage of commissioning 2 6 Step 5 Testing 2 6 1 Fault Test This is done to confirm that the returned signal is from the reflector Cover the entire refle...

Страница 12: ...it will reset to normal automatically FAULT The beam path has been fully blocked within 1 second used when fault testing in commissioning ERROR No communication with the controller This could be that...

Страница 13: ...ress down to go through the main menu options Select this option to change system language Select this option to commission the ESP FIREbeam Select this option to make all changes and adjustments to t...

Страница 14: ...automatically stop when a received signal strength reaches 6 this received signal is the returned strength of the output signal without a reflector if no return signal is received the beam will reach...

Страница 15: ...ved signal raises above the fire threshold hysteresis This can be set to latching if your system requires this Change by using the right and left keys Press enter to return to Mode Change or down to g...

Страница 16: ...enter to return to Mode Change or down to go to Hysteresis Hysteresis Changing the hysteresis will change the delay in returning from a fire state back to a normal state For example the beam is facto...

Страница 17: ...to Beam Maintenance or down to go to Alarm Fault Event Counts Alarm Fault Event Counts Here we can see how many times the beam has gone into fire or fault since the beam was commissioned or since the...

Страница 18: ...t and left keys Press enter to return to Diagnostics or down to go to RX Sensitivity RX Sensitivity This screen shows the receiver sensitivity and can be changed by using the right and left keys Press...

Страница 19: ...larm Condition adjustable 2 to 30 seconds in 1 second increments default 10 seconds Alarm Indication Controller Status FIRE Controller Red Flashing LED Head Red Flashing LED Alarm Relay Change Over CO...

Отзывы: