  ESP FIREbeam – Installation Manual 

 2011 Hochiki Europe (UK) Ltd 

2-3-0-1340/ISS2/DEC11 

    

 

NOW place or uncover the reflector on the blank wall directly opposite the beam head ensuring there is a clear path 
through any obstructions such as structural steels etc. 

NOTE: It is important that there is a clear line of sight between the reflector and beam head.  The beam must see 

at least 200mm of clear space around the reflector to enable the beam to see the edges of the reflector to 
allow successful auto alignment in the following stage. 

Once the reflector is in place and visible there should be a big jump in the received signal (AQ).  This means that 
the head is seeing and receiving a signal back from the reflector.  In most cases this will result in a received signal 
of over 100%. 

 

 

As long as there is a received signal of over 40% you can move onto the next stage, see “Stage Four - Auto-
Alignment” on page 11. 

If the AQ reading is below 40% it means the head is not seeing the reflector and will abort Auto Alignment.  The 
next stage is to manually move the beam to achieve an AQ reading of over 40%, ideally over 100%.  The higher 
the AQ the quicker it will auto align.  This is done by manually moving the x and y motors to obtain a received 
signal from the reflector. 

In the example below we can see that the reflector is below the eye line of the beam head, so in this case you 
would need to lower the angle of the beam (-Y) until you receive an AQ of over 40%. 

 

The beam can be moved on both X and Y axis to a maximum 5 degrees using the 

left

 (x-), 

right

 (x+), 

up

 (y+) 

and

 

down

 (y-)

 keys.  Looking at the reflector this 

will move the beam across the reflector as shown: 

Holding the keys down will quickly scroll through to your desired position, on release of the button the screen will 
revert to the actual beam position and can be seen stepping toward the requested position. 

To confirm the beam is seeing the reflector, cover the reflector as this should drop the AQ and therefore prove the 
beam is on the reflector. 

In the example above moving the y axis down (y-) 
results in a greater AQ 

Try and achieve as high an AQ as possible, it must be 
over 40% to auto align. The higher the AQ the quicker 
the auto align, above 100% is good 

 

 

You will now see the manual alignment screen showing anything between 0 and 6%. This is the amount of received 
signal with no reflector that the beam is picking up from the environment. 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание ESP FIREbeam

Страница 1: ...esp FIREbeam INSTALLATION MANUAL www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...www acornfiresecurity com www acornfiresecurity com...

Страница 3: ...2 Step 2 Programming the Analogue Address 6 2 3 Step 3 Mounting the Controller 7 2 4 Wiring Configuration 7 2 5 Step 4 Commissioning 8 2 5 1 Stage One Language and Commissioning Speed 8 2 5 2 Stage T...

Страница 4: ...ESP FIREbeam comes boxed with the head unit low level controller one reflector 3mm allen key and quick start installation guide this should be used for distances over 5m and up to 40m 1 1 2 40 to 80 m...

Страница 5: ...40m from the floor The maximum protected area either side of the beam can be extended by 1 for every degree of roof pitch see the example below NOTE Careful design consideration should be made when p...

Страница 6: ...the front edge of the box Wire to low level controller using bottom colour coded terminals Screw in through holes provided outside of the rubber seal 2 2 Step 2 Programming the Analogue Address The F...

Страница 7: ...this connection can be checked by reading the resistance across the black and grey terminals they will read 110 ohm if OK or 220 ohm if not connected properly 2 4 Wiring Configuration The output curre...

Страница 8: ...in normal mode the system uses 3 5mA in fast mode it uses 17mA if you are commissioning more than one beam at a time and the system cannot support the extra draw it may be necessary to use normal mod...

Страница 9: ...ng noticeably less read on below These figures are approximate but if you are receiving noticeably less than these figures you may be receiving a reflection from an object nearby and not the far wall...

Страница 10: ...higher the AQ the quicker it will auto align This is done by manually moving the x and y motors to obtain a received signal from the reflector In the example below we can see that the reflector is bel...

Страница 11: ...low 100 Now proceed to Step 4 Testing the final stage of commissioning 2 6 Step 5 Testing 2 6 1 Fault Test This is done to confirm that the returned signal is from the reflector Cover the entire refle...

Страница 12: ...it will reset to normal automatically FAULT The beam path has been fully blocked within 1 second used when fault testing in commissioning ERROR No communication with the controller This could be that...

Страница 13: ...ress down to go through the main menu options Select this option to change system language Select this option to commission the ESP FIREbeam Select this option to make all changes and adjustments to t...

Страница 14: ...automatically stop when a received signal strength reaches 6 this received signal is the returned strength of the output signal without a reflector if no return signal is received the beam will reach...

Страница 15: ...ved signal raises above the fire threshold hysteresis This can be set to latching if your system requires this Change by using the right and left keys Press enter to return to Mode Change or down to g...

Страница 16: ...enter to return to Mode Change or down to go to Hysteresis Hysteresis Changing the hysteresis will change the delay in returning from a fire state back to a normal state For example the beam is facto...

Страница 17: ...to Beam Maintenance or down to go to Alarm Fault Event Counts Alarm Fault Event Counts Here we can see how many times the beam has gone into fire or fault since the beam was commissioned or since the...

Страница 18: ...t and left keys Press enter to return to Diagnostics or down to go to RX Sensitivity RX Sensitivity This screen shows the receiver sensitivity and can be changed by using the right and left keys Press...

Страница 19: ...larm Condition adjustable 2 to 30 seconds in 1 second increments default 10 seconds Alarm Indication Controller Status FIRE Controller Red Flashing LED Head Red Flashing LED Alarm Relay Change Over CO...

Отзывы: