Before  installing  the  system  the  following  points 
need to be considered. 

The  communication  range  between  the  translator, 
expanders,  and  all  wireless  devices  is  specified  in 
‘free air’.  The range will vary and generally decrease 
when installed within building structures. 

It is recommended that preliminary system design is 
made on paper. Optimum device positioning can be 
verified during installation and additional expanders 
can be added if required. 

The  number  of  translators  /  expanders  required  is 
determined  by  the  number  of  wireless  devices 
connected  to  the  control  panel  and  the 
communication  range  between  the  translators  / 
expanders and wireless devices. 

EK‐WL8‐EXP expanders should be used when 

 

some  wireless  devices  are  too  far  from  the 
translator 

 

the  translator’s  communication  range  does  not 
cover  the  necessary  territory  (e.g.  the  whole 
building or one of the floors) 

 

connection with wireless devices is weakened by 
external electromagnetic interference 

 

the building has thick walls, metallic structures or 
other  objects  that  significantly  lower  the 
communication  range  of  the  translator  and 
wireless devices 

 

backup  and  alternative  communication  routes 
need to be provided in the system 

The  system  designer  needs  to  evenly  disperse 
expanders across the premises in order to provide a 
stable connection to the network in every part of the 
building. Wireless devices will automatically choose 
the closest expander that will provide the strongest 
connection. 

When  designing  a  wireless  fire  alarm  system,  it  is 
important to keep in mind that the communication 
range 

between 

different 

wireless 

devices 

significantly depends on walls and obstacles that can 
block  radio  communication.  This  is  why  it  is 
recommended  to  check  the  connection  strength 
between  different  rooms  in  the  building  before 
designing and installing the system. 

Using Expanders 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание ekho

Страница 1: ...Wireless Fire Alarm System Installation Guide www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...llation Guidelines 6 Frequency Channels and Traffic 7 Connecting the Translator 7 Addressing 8 Programming and Servicing in Translator Menu 9 EKHO Configurator Getting Started 11 Programming Devices 1...

Страница 3: ...ire alarm condition EK WL8 IN Input modules receive a signal from wired conventional non addressable sensors and devices and transmit them to the translator EK WL8 OUT Output modules receive control c...

Страница 4: ...ween two expanders 2000 m Communication range between a translator or expander and a wireless device 1200 m Maximum number of expanders connected sequentially one after another 10 Maximum number of ex...

Страница 5: ...g or one of the floors connection with wireless devices is weakened by external electromagnetic interference the building has thick walls metallic structures or other objects that significantly lower...

Страница 6: ...nsure the strongest communication signal Connection strength can be viewed via the translator s display or the software Select a frequency channel that is free or relatively free of interference and a...

Страница 7: ...translator and the wireless devices connected to it make up an independent wireless system If the fire control panel has several translators connected to it then it would be possible that some of them...

Страница 8: ...The numbering will begin with the starting address of the translator For example if the starting address is 1 the following wireless devices that are added to the system will be given address 2 3 4 5...

Страница 9: ...SW Change sub menu Adding devices To add a new device in the system use the ADD command in the Configuration menu Changing settings Each device has different settings such as the sensitivity of smoke...

Страница 10: ...u to check the state of devices generate a test alarm and send different control commands For more information on how to use the hardware menu on the translator please refer to its manual www acornfir...

Страница 11: ...s all information on the system Select WL8 TRV and choose USB port in the right window Send the Program command to the translator After the programming is complete press Activate event protocoling so...

Страница 12: ...lator to add new devices Press Initialize to link the device with the translator After pressing the Prog button on the device it will appear in the pop up window Select it and press Continue to confir...

Страница 13: ...security you will need to enter a password in order to initialize the device The password can be found on the label on the device Indication section includes parameters allowing you to turn on off LED...

Страница 14: ...update Primary standby supply voltage level of the main and the backup battery Fault current state of the device Analog value and Analog type will contain different values based on the type of the de...

Страница 15: ...a month The Problems column will now display the number of faults and alarms that occurred in that time frame for each of the devices You can sort the table by this column so that the devices that ne...

Страница 16: ...ain device Wireless Connections The EKHO Configurator software allows you to analyze the network topology and connection strength with wireless devices in real time To do that go to the Wireless conne...

Страница 17: ...l system the base level of the Signal graph should fall in the range from 110 to 90 dBm and Traffic should not exceed 10 The network topology window shows how wireless devices are interconnected with...

Отзывы: