Intesis
TM
KNX
– HITACHI VRF
User Manual r1.1 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
31 / 32
INDOOR UNIT
SIGNALS
Control_Vane position auto
1 bit
DPT_Switch
1.001
R
T
1-Set auto vane, 0-Stop auto vane
Status_Vane position auto
1 bit
DPT_Switch
1.001
W
1-Vane auto active, 0-Vane auto not active
Control_Vane position position-1
1 bit
DPT_Switch
1.001
R
T
1-Set position-1 vane
Status_Vane position position-1
1 bit
DPT_Switch
1.001
W
1-Vane position-1 active, 0-Vane position-1 not active
Control_Vane position position-2
1 bit
DPT_Switch
1.001
R
T
1-Set position-2 vane
Status_Vane position position-2
1 bit
DPT_Switch
1.001
W
1-Vane position-2 active, 0-Vane position-2 not active
Control_Vane position position-3
1 bit
DPT_Switch
1.001
R
T
1-Set position-3 vane
Status_Vane position position-3
1 bit
DPT_Switch
1.001
W
1-Vane position-3 active, 0-Vane position-3 not active
Control_Vane position position-4
1 bit
DPT_Switch
1.001
R
T
1-Set position-4 vane
Status_Vane position position-4
1 bit
DPT_Switch
1.001
W
1-Vane position-4 active, 0-Vane position-4 not active
Control_Vane position position-5
1 bit
DPT_Switch
1.001
R
T
1-Set position-5 vane
Status_Vane position position-5
1 bit
DPT_Switch
1.001
W
1-Vane position-5 active, 0-Vane position-5 not active
Control_Vane position position-6
1 bit
DPT_Switch
1.001
R
T
1-Set position-6 vane
Status_Vane position position-6
1 bit
DPT_Switch
1.001
W
1-Vane position-6 active, 0-Vane position-6 not active
Control_Vane position position-7
1 bit
DPT_Switch
1.001
R
T
1-Set position-7 vane
Status_Vane position position-7
1 bit
DPT_Switch
1.001
W
1-Vane position-7 active, 0-Vane position-7 not active
TEMPERATURES
Control_Temperature Setpoint (ºC)
2 byte
DPT_Value_Temp
9.001
W
Cool:19..30 ºC; Heat:17..30 ºC
Status_Temperature Setpoint (ºC)
2 byte
DPT_Value_Temp
9.001
R
T
Cool:19..30 ºC; Heat:17..30 ºC
Status_AC Ambient Temperature (ºC)
2 byte
DPT_Value_Temp
9.001
R
T
-63..63 ºC
Status_Remote Sensor Temperature (ºC)
2 byte
DPT_Value_Temp
9.001
R
T
-63..63 ºC
Control_KNX ambient Temperature (ºC)
2 byte
DPT_Value_Temp
9.001
W
ºC
Status_Outlet Temperature (ºC)
2 byte
DPT_Value_Temp
9.001
W
-63..63 ºC
Status_GasPipe Temperature (ºC)
2 byte
DPT_Value_Temp
9.001
R
T
-63..63 ºC
Status_LiquidPipe Temperature (ºC)
2 byte
DPT_Value_Temp
9.001
W
-63..63 ºC
ERROR CODE
Status_Unit error
1 bit
1.005-DPT_Alarm
1.005
R
T
0-No error, 1-Error
Status_Unit error code
2 byte
Non-standarized
8.x
R
T
0-No Error, X-Error (100..999)
FILTER
Status_FilterSign
1 bit
DPT_Alarm
1.005
R
T
0-Normal, 1-Alarm
Control _FilterReset
1 bit
DPT_Reset
1.015
W
0-No reset, 1-Reset
COMM STATUS
Status_Communication status
1 bit
DPT_Switch
1.001
R
T
0-Not exist, 1-Exist