Error codes for Indoor and Outdoor Units 

This list contains all possible values shown in KNX Object for “Error Code” for each indoor unit and outdoor unit. 
 
It must be taken into account that Outdoor Units are only able to reflect a single error for each indoor / outdoor unit in 
the system. Thus, a unit having two or more active errors from that list will only report a single error code 

– the one of 

the first error that has been detected. 
 

Error 
Code

 

Category

 

Content of Abnormality

 

Leading Cause

 

 

01

 

 

lndoor Unit

 

 

Activation of Protection Device (Float 
Switch)

 

Activation of Float Switch

 

(High Water Level in Drain Pan

,

 

Abnormality of Drain Pipe

Float Switch or 

Drain Pan)

 

02

 

 

Outdoor Unit

 

Activation of Protection 
Device (High Pressure 
Cut)

 

Activation of PSH (Pipe Clogging

Excessive Refrigerant!

 

lnert Gas 

Mixing)

 

03

 

 
 
 

Transmission

 

 

Abnormality between lndoor and 
Outdoor

 

incorrect Wiring

Loose Terminals

Disconnect Wire

Blowout of Fuse

Outdoor Unit Power OFF

 

 

04

 

 

Abnormality between lnverter PCB 
and Outdoor PCB

 

lnverter PCB - Outdoor PCB 
Transmission Failure (Loose Connector

Wire Breaking

Blowout of Fuse)

 

04.

 

Abnormality between Fan Controller 
and Outdoor PCB

 

Fan Controller - Outdoor PCB 
Transmission Failure (Loose Connector

Wire Breaking

Blowout of Fuse)

 

05

 

Supply Phase

 

Abnormality Power Source Phases

 

lncorrect Power Source

Connection to Reversed 
Phase

Open-Phase

 

06

 

 

Voltage

 

Abnormal lnverter 

Voltage

 

Outdoor Voltage Drop

insufficient Power 

Capacity

 

06.

 

Abnormal Fan Controller 

Voltage

 

Outdoor Voltage Drop

lnsufficient Power 

Capacity

 

 

07

 

 
 
 
 

Cycle

 

 
 

Decrease in Discharge Gas Superheat

 

Excessive Refrigerant! Charge

Failure of 

Thermistor

lncorrect Wiring

lncorrect 

Piping Connection

Expansion Valve 

Locking at Opened Position (Disconnect 
Connector)

 

 

08

 

 
 

lncrease in Discharge Gas 
Temperature

 

lnsufficient Refrigerant! Charge

Pipe Clogging, Failure of 
Thermistor

lncorrect Wiring

,

 

lncorrect Piping Connection

Expansion 

Valve Locking at Closed Position 
(Disconnect Connector)

 

0A

 

Transmission

 

Abnormality between Outdoor and 
Outdoor

 

lncorrect Wiring

Breaking Wire

Loose Terminals

 

0b

 

 
 

Outdoor Unit

 

lncorrect Outdoor Unit Address 
Setting

 

Duplication of Address Setting for 
Outdoor Units (Sub Units) in Same 
Refrigerant! Cycle System

 

0c

 

lncorrect Outdoor Unit Main Unit 

Two (or more) Outdoor Units Set 

Содержание Intesis KNX HITACHI VRF

Страница 1: ...HITACHI VRF Air Conditioning Gateway for the integration of Hitachi VRF systems into KNX home automation systems USER MANUAL Issue date 11 2020 r1 2 ENGLISH...

Страница 2: ...d are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many variables a...

Страница 3: ...All rights reserved This information is subject to change without notice URL https www intesis com 3 32 Gateway for the integration of Hitachi VRF systems into KNX home automation systems ORDER CODE...

Страница 4: ...and troubleshooting 11 Pre requisites 11 Intesis MAPS Configuration monitoring tool for Intesis KNX series 11 4 2 1 Introduction 11 4 2 2 Connection 11 4 2 3 Configuration tab 12 4 2 4 KNX configurati...

Страница 5: ...ntegration is to monitor and control your Hitachi air conditioning system from your KNX TP 1 installation To do it so Intesis performs as a one more KNX device sending and receiving telegrams to group...

Страница 6: ...network for all configured signals and keeps the updated status of all of them in its memory It triggers updates on configured group addresses to KNX network on value change Commands toward the indoor...

Страница 7: ...Element Max Notes Number of indoor units 64 Number of indoor units that can be controlled through Intesis There are different models of Intesis KNX Hitachi VRF each one with different capacity The tab...

Страница 8: ...on object See details below Points definition Every group object in configuration has following KNX properties Property Description Description Descriptive information about the communication object o...

Страница 9: ...Connect the cable coming from the IP network to the connector ETH of the gateway Use an Ethernet CAT5 cable If communicating through the LAN of the building contact the network administrator and make...

Страница 10: ...earth The use of AC power supplies only if they are floating and not powering any other device Connect to Hitachi installation Use the Port B connector of the Intesis device to connect Hitachi H Link...

Страница 11: ...is gateway Link to download the configuration tool USB Console cable to communicate with Intesis Product documentation Intesis MAPS Configuration monitoring tool for Intesis KNX series 4 2 1 Introduct...

Страница 12: ...ation tab Select the Configuration tab to configure the connection parameters Three subsets of information are shown in this window General Gateway general parameters KNX KNX interface configuration a...

Страница 13: ...objects the corresponding operating mode and ON operation is sent to the indoor unit Whenever both values are 0 indoor unit is set to OFF 2 3 Use of 1 bit Operating Modes 1 bit Control Objects Enables...

Страница 14: ...Fan Speed 1 bit Control Objects Enables a bit type object for control of fan speed 4 5 Use of 1 bit Fan Speed 1 bit Status Objects Enables a bit type object for monitoring of each fan speed 5 Vanes P...

Страница 15: ...munication with H Link The faster way to import the units present in the H Link bus is to Autodiscover them To do so click button Scan and the following window will appear Figure 4 4 Intesis MAPS Scan...

Страница 16: ...igure 4 5 Intesis MAPS Scan Hitachi Units window with scan results Select with its checkbox units to add or replace in installation according to selection Replace Units Add Units After units to be int...

Страница 17: ...re included to overcome any issue detected for certain installations These parameters are Time Interframe Minimum time between received and sent frames 0 100 000 Retry timeout Minimum time before laun...

Страница 18: ...sis model IU address Address 1 64 of Unit in Hitachi H Link bus OU address Address 1 64 of Outdoor Unit in Hitachi H Link bus CSNETid only for CS NET Manager configuration in this column the AC addres...

Страница 19: ...M KNX HITACHI VRF User Manual r1 2 EN HMS Industrial Networks S L U All rights reserved This information is subject to change without notice URL https www intesis com 19 32 Figure 4 9 Intesis MAPS Sig...

Страница 20: ...Send button in the Receive Send section 4 2 8 Diagnostic To help integrators in the commissioning tasks and troubleshooting the Configuration Tool offers some specific tools and viewers In order to st...

Страница 21: ...S Industrial Networks S L U All rights reserved This information is subject to change without notice URL https www intesis com 21 32 Figure 4 11 Diagnostic More information about the Diagnostic sectio...

Страница 22: ...ted to it we strongly recommend The use of DC power supplies floating or with the negative terminal connected to earth Never use a DC power supply with the positive terminal connected to earth The use...

Страница 23: ...r 1 x Plug in screw terminal block 3 poles 9 to 36VDC 10 Max 140mA 24VAC 10 50 60Hz Max 127mA Recommended 24VDC Push Button Button A Check the user manual Button B Check the user manual Operation Temp...

Страница 24: ...served This information is subject to change without notice URL https www intesis com 24 32 6 Dimensions Recommended available space for its installation into a cabinet wall or DIN rail mounting with...

Страница 25: ...tion is subject to change without notice URL https www intesis com 25 32 7 AC Unit Types compatibility A list of Hitachi unit model references compatible with INKNXHIT016O000 INKNXHIT064O000 and their...

Страница 26: ...OFF 04 Abnormality between lnverter PCB and Outdoor PCB lnverter PCB Outdoor PCB Transmission Failure Loose Connector Wire Breaking Blowout of Fuse 04 Abnormality between Fan Controller and Outdoor P...

Страница 27: ...Designed for R22 38 Abnormality of Picking up Circuit for Protection in Outdoor Unit Failure of Protection Detecting Device lncorrect Wiring of Outdoor PCB 39 Compressor Abnormality Running Current at...

Страница 28: ...eat Exchanger Clogging Fan Motor Failure 5b Activation of Overcurrent Protection Fan Motor Failure 5C Abnormality of Fan Controller Sensor Failure of Current Sensor lnstantaneous Overcurrent lncrease...

Страница 29: ...arm 1 005 R T 0 No error 1 Error TEMPERATURES Status_Outdoor Air Temperature C 2 byte DPT_Value_Temp 9 001 R T 50 99 C Status_Compresor Top Temperature C 2 byte DPT_Value_Temp 9 001 R T 0 200 C COMPRE...

Страница 30: ...igh 4 High Control _Fan speed scaling 1 byte DPT_Scaling 5 001 W Thersholds 0 37 38 62 63 87 88 100 Status _Fan speed scaling 1 byte DPT_Scaling 5 001 R T Thersholds 25 50 75 100 Control_ Fan speed lo...

Страница 31: ...ition 5 1 bit DPT_Switch 1 001 W 1 Vane position 5 active 0 Vane position 5 not active Control_Vane position position 6 1 bit DPT_Switch 1 001 R T 1 Set position 6 vane Status_Vane position position 6...

Страница 32: ...sablement 1 bit DPT_Bool 1 002 W 0 No disabled 1 Disabled Status_Fan Remote controll disablement 1 bit DPT_Bool 1 002 R T 0 No disabled 1 Disabled SYSTEM INFO Status_Unit type 1 byte DPT_Value_1_Ucoun...

Отзывы: