Doc.Id. SCM-1200-080
Anybus X-gateway CANopen - PROFIBUS
Doc.Rev. 1.02
Appendix A
A. Technical Specification
A.1 Protective Earth (PE) Requirements
The product must be connected to protective earth (PE) via the DIN-rail connector in order to achieve
proper EMC behavior.
HMS Industrial Networks does not guarantee proper EMC behavior unless these PE requirements are
fulfilled.
A.2 Power Supply
Supply Voltage
The gateway requires a regulated 24 V±10% DC power source.
Power Consumption
The maximum power consumption is 150 mA at 24 V.
A.3 Environmental Specification
A.3.1 Temperature
Operating
-25
º
to +55
º
Celsius
(Test performed according to IEC-60068-2-1 and IEC 60068-2-2.)
Non Operating
-40
º
to +85
º
degrees Celsius
(Test performed according to IEC-60068-2-1 and IEC 60068-2-2.)
A.3.2 Relative Humidity
The product is designed for a relative humidity of 5 to 95% non-condensing.
Test performed according to IEC 60068-2-30.