background image

Page 6 

CAUTION: It is mandatory to abide by clearance to combustibles regulations provided on the 
furnace label and in this instruction manual.  Failure to abide by the clearance requirements may 
result in a fire. 
 
Requirements In Regards To Installation: 

 

DO NOT connect to a chimney serving another appliance. Only one appliance is to be used per 
chimney. 

 

Flue must be the same size as stove flue collar or larger within requirements of flue size 
maximums. 

 

Chimney connector pipe (stove pipe) must be made of at least 24 gauge metal and be attached 
with crimped ends facing the stove.  A minimum of 3 screws is required at each connection point. 

 

Masonry or manufactured thimble must be longer than the thickness of the wall and does not 
intrude past the inner face of the chimney liner.  

 

Thimble 

may be constructed of approved clay liner thimble tested and labeled. With a 12” non-

combustible clearance zone on each side of thimble. Please use NFPA 211 instructions and 
requirements in regarding thimble information. 

 

Thimble may be a manufactured thimble or class A chimney pipe. A manufactured component 
must be installed with listed components accessories and meet manufacturer’s specifications. 

 

It is required to have thimble clearances to combustible material as required by manufacturer and 
NFPA 211. 

 

NF

PA 211 codes must be followed and an 18” clearance to combustible material is required for 

chimney connectors. 

 

This unit must be installed on a noncombustible floor according to the measurements above.  

 

DO NOT install in a garage. 

 

Connecting Furnace To Chimney:

  

Connection of your Energy Master Furnace to the chimney should be made as direct as possible.  It is not 
recommended to use more then 2 elbows for venting. The pipe connecting the furnace to the chimney 
should be at least 24 gauge single wall pipe. Thicker gauges and double wall pipe may be used. A ½  
inch slope, back toward the furnace, per foot of horizontal run

 

is required.  This allows any condensation 

forming in the pipe to flow back toward the furnace. The connection pipe should be installed so the upper 
pipe fits inside the lower pipe. Horizontal run pipe should have the seam turned up.  Note the point at 
which the

 

flue passes through a wall to the chimney. This penetration must be made with an approved 

through the wall thimble or class A chimney pipe and used with the listed proper accessories according to 
manufacturer’s instructions. Chimney connector (stove pipe) CANNOT pass through a ceiling, wall, or any 
concealed space. Three screws must be attached at each connection point of the chimney connector. 
When the Class A chimney pipe connects to the masonry, it must be cemented to the chimney, or a 
thimble must be connected to the chimney and the pipe should be tightly inserted into the thimble without 
cementing.  
 

III. Typical Installations  

 

 
Illustrations:

 

Below are typical ways of installation formats.  Note: these illustrations reflect typical installations and are 
for design purposes only. Illustrations and diagrams are for informational purposes only.  These diagrams 
are not drawn to scale.  Actual installation procedures may vary.

 

 
NOTE:  

It is always best to run the supply duct up.  The supply duct must be constructed of material with 

a minimum 250

°

 temperature rating. With the supply duct up, this will allow gravity heat to still rise into 

the system.  The plenum on the furnace must be constructed of metal. 

 
 
 
 
 

Содержание Energy Master II 710

Страница 1: ...SONAL INJURY OR EVEN DEATH REFER TO MARKINGS ON THE FURNACE FOR ADDITIONAL INFORMATION CARBON MONOXIDE AND SMOKE DETECTORS ALARMS MUST BE INSTALLED IN THE HOME AND WORKING PROPERLY DANGER RISK OF FIRE OR EXPLOSION DO NOT BURN GARBAGE GASOLINE DRAIN OIL OR OTHER FLAMMABLE LIQUIDS DO NOT USE CHEMICALS OR FLUIDS TO START FIRE BURN RICE SIZE ANTHRACITE COAL ONLY STOVE SURFACES MAY BE HOT WHILE IN OPER...

Страница 2: ...eturn Air D Combustion Air E Installation In A Confined Space IV Flue Systems A Masonry System B Factory Built Systems C Chimney Requirements D Flue Size E Chimney Height Requirements F Power Vent System V Basic Regulations for Safe Operations A Cautions B Local Codes VI Stove Start Up Operation A Install Coal Trol Thermostat B Start Up C Adjusting Chimney Draft D Measuring Furnace Compatibility V...

Страница 3: ...fire follow the installation instructions carefully Failure to follow these instructions may result in property damage bodily injury or even death Contact your local building inspector or fire officials about the need for a permit restrictions or installation inspection required in your area Refer to makings on your furnace for more information Save these instructions for future reference Safety N...

Страница 4: ... Once it is determined your existing furnace will accept an add on installation a parallel installation with return air outlined later in this manual is recommended 3 Can the furnace be vented properly a Is the chimney appropriate for this installation This furnace requires installation in a masonry chimney with a clay flue liner or a metal all fuel chimney listed to UL103 CAN ULC S629 M87 Type HT...

Страница 5: ...ated and make placement of the Energy Master Furnace to achieve maximum heat benefit it can produce Clearances To Combustibles Floor Protection This furnace must be placed on a non combustible floor If the floor is a combustible material floor protection must be placed underneath it and extend at least 8 inches on each side of the fuel or ash door It must also extend 16 inches out from the front o...

Страница 6: ...ter Furnace to the chimney should be made as direct as possible It is not recommended to use more then 2 elbows for venting The pipe connecting the furnace to the chimney should be at least 24 gauge single wall pipe Thicker gauges and double wall pipe may be used A inch slope back toward the furnace per foot of horizontal run is required This allows any condensation forming in the pipe to flow bac...

Страница 7: ...Page 7 ...

Страница 8: ...are drawn with a masonry chimney Manufactured metal chimney listed to UL 103 CAN ULC S629 M87 Type HT or a Hitzer approved power vent system may also be used Follow manufacturer s instructions guidelines when using these products ...

Страница 9: ...our basement unnecessarily heating unused portions of your home The return duct should be a minimum of 16 x 20 or equivalent 320sq in The return duct may be attached to the rear of the stoker furnace Make sure if you are attaching the duct to the rear of the furnace you do not inhibit the removal and replacement of the furnace filters These filters should be checked and cleaned replaced regularly ...

Страница 10: ... Supplemental add on Furnace Installations Do not use duct elbows having an inside radius of less than 6in 150mm on the oil gas electric furnace Do not connect to a down flow furnace Do not connect ductwork so that a reverse flow is possible Operate the gas oil electric furnace periodically to ensure it will operate satisfactorily when needed Certified for installation with the ductwork configurat...

Страница 11: ... only have one appliance per chimney and it is not permissible to connect your Hitzer Energy Master II furnace to a chimney that is servicing another appliance Flue Requirements It is required to have a chimney that is built according to the chimney manufacturer s specifications and meets local building codes It is also required to have your chimney inspected and cleaned by a certified chimney pro...

Страница 12: ...our draft A few of these include wind speed and direction obstructions diverting winds barometric pressure and humidity This is why it is essential to have a barometric damper and carbon monoxide detectors alarms installed and working properly Power Vent System A Hitzer approved power vent may be used in place of a chimney BE SURE TO READ YOUR POWER VENTER INSTALLATION AND OPERATION INSTRUCTION MA...

Страница 13: ...he properly constructed and in good top of the fire box When the door is condition Chimney must be at least 15 opened oxygen combines with gases high and exceed the roof a minimum of and ignites 3 feet unless using Power Vent System WARNING Risk of Fire WARNING Over Fire Unit Comply with all minimum clearances to Do NOT over fire your unit combustibles as specified This will cause warping of fire ...

Страница 14: ... hole to read the chimney draft Adjust the barometric damper so that your manometer reads between 03 and 06 inches of water column following the instructions provided with the damper Do not run at a draft above 06 inches of water column as this could cause your stoker to over fire Over firing can cause a dangerous fire hazard It would be best to set it with a manometer if available The settings on...

Страница 15: ...amount of coal burned ash content of the coal the burn rate and draft of the chimney Allow stoker to run out of coal go out and cool down Remove chimney connector pipes and check and remove any fly ash accumulation This will mainly be at the bottom of elbows and horizontal runs Remove all fly ash from heat exchanger plates inside and below the flue collar and on the floor of the stoker around the ...

Страница 16: ...Page 16 VI Troubleshooting ...

Страница 17: ...rmined by the capacity and condition of the battery and the amount of heat needed Some generators will also work however the output of either must be a pure sine wave Other outputs can cause the Coal Troll Digital to not work You may also contact your Hitzer dealer or Hitzer Inc for questions or more information regarding stove installation and operation Hitzer Inc 269 E Main St Berne IN 46711 260...

Отзывы: