Hitzer Energy Master II 710 Скачать руководство пользователя страница 5

Page 5 

Location: 

The location of the stove is very important for optimum stove performance as well as safety assurance.  

When searching for the location of the stove be sure to strictly follow manufactures guidelines, 
clearance to combustible material requirements, local building, and fire codes.  Failure to follow 
manufacture’s instruction and local jurisdiction codes may result in bodily injury, property 
damage, fire, or death.

  Locate the stove where there is sufficient air supply for proper operation to 

occur. It is vitally important to locate the stove next to existing forced air furnace as well as next to the 
chimney, or exterior wall for power vent systems.   The closer placement to these two items the better the 
stove will perform, and achieve maximum heat flow.  The longer the chimney connector pipe (stovepipe) 
and farther away the furnace is from the chimney or power vent the less performance is achieved from 
the furnace. Please consider the construction and layout of the home to be heated and make placement 
of the Energy Master Furnace to achieve maximum heat benefit it can produce.    

 
Clearances To Combustibles/Floor Protection: 

This furnace must be placed on a non-combustible floor. If the floor is a combustible material floor 
protection must be placed underneath it and extend at least 8 inches on each side of the fuel or ash door.  
It must also extend 16 inches out from the front of the furnace. The floor protection must also be placed 
underneath the chimney

 

connector (stove pipe) and extend at least 2 inches on either side of the chimney 

connector.  This protection is for hot ash and sparks. It is not needed for heat protection. If your furnace is 
installed on a concrete basement floor, it is recommended to install on a 2 inch thick nonflammable 
material. This will reduce contact with the damp floor that can cause possible rust and corrosion.  
 

 
    

 

 

 

 

Back wall 

 

 

 

 

 

 

 

    

 

           

 

 

 

 

                         

 

 

2” 

 

 

 

 

 

 

 

     

 

  

 

 

 

 

 

 

 

               

  

     

 

 

 

 

 

 

 

 

 

 

 

 

       

    

 

 

 

 

 

 

 

 

 

 

 

 

 

     

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Clearance to Combustible Material: 

 

 

Floor Protection: 

Unit to Side Wall:  2 inches 

 

 

 

 

Front: 16 inches 

Unit to Back Wall: 6 inches 

 

 

 

 

Side: 8 inches from  

Chimney Connecter to Back Wall: 18 inches  

 

             either side of the  

Chimney Connecter to Side Wall: 18 inches   

 

             fuel and ash door 

 

                                                                                                      Rear: 2 inches 
 

Furnace 

Floor Protection 

16 “ 

8” 

6” 

2” 

Содержание Energy Master II 710

Страница 1: ...SONAL INJURY OR EVEN DEATH REFER TO MARKINGS ON THE FURNACE FOR ADDITIONAL INFORMATION CARBON MONOXIDE AND SMOKE DETECTORS ALARMS MUST BE INSTALLED IN THE HOME AND WORKING PROPERLY DANGER RISK OF FIRE OR EXPLOSION DO NOT BURN GARBAGE GASOLINE DRAIN OIL OR OTHER FLAMMABLE LIQUIDS DO NOT USE CHEMICALS OR FLUIDS TO START FIRE BURN RICE SIZE ANTHRACITE COAL ONLY STOVE SURFACES MAY BE HOT WHILE IN OPER...

Страница 2: ...eturn Air D Combustion Air E Installation In A Confined Space IV Flue Systems A Masonry System B Factory Built Systems C Chimney Requirements D Flue Size E Chimney Height Requirements F Power Vent System V Basic Regulations for Safe Operations A Cautions B Local Codes VI Stove Start Up Operation A Install Coal Trol Thermostat B Start Up C Adjusting Chimney Draft D Measuring Furnace Compatibility V...

Страница 3: ...fire follow the installation instructions carefully Failure to follow these instructions may result in property damage bodily injury or even death Contact your local building inspector or fire officials about the need for a permit restrictions or installation inspection required in your area Refer to makings on your furnace for more information Save these instructions for future reference Safety N...

Страница 4: ... Once it is determined your existing furnace will accept an add on installation a parallel installation with return air outlined later in this manual is recommended 3 Can the furnace be vented properly a Is the chimney appropriate for this installation This furnace requires installation in a masonry chimney with a clay flue liner or a metal all fuel chimney listed to UL103 CAN ULC S629 M87 Type HT...

Страница 5: ...ated and make placement of the Energy Master Furnace to achieve maximum heat benefit it can produce Clearances To Combustibles Floor Protection This furnace must be placed on a non combustible floor If the floor is a combustible material floor protection must be placed underneath it and extend at least 8 inches on each side of the fuel or ash door It must also extend 16 inches out from the front o...

Страница 6: ...ter Furnace to the chimney should be made as direct as possible It is not recommended to use more then 2 elbows for venting The pipe connecting the furnace to the chimney should be at least 24 gauge single wall pipe Thicker gauges and double wall pipe may be used A inch slope back toward the furnace per foot of horizontal run is required This allows any condensation forming in the pipe to flow bac...

Страница 7: ...Page 7 ...

Страница 8: ...are drawn with a masonry chimney Manufactured metal chimney listed to UL 103 CAN ULC S629 M87 Type HT or a Hitzer approved power vent system may also be used Follow manufacturer s instructions guidelines when using these products ...

Страница 9: ...our basement unnecessarily heating unused portions of your home The return duct should be a minimum of 16 x 20 or equivalent 320sq in The return duct may be attached to the rear of the stoker furnace Make sure if you are attaching the duct to the rear of the furnace you do not inhibit the removal and replacement of the furnace filters These filters should be checked and cleaned replaced regularly ...

Страница 10: ... Supplemental add on Furnace Installations Do not use duct elbows having an inside radius of less than 6in 150mm on the oil gas electric furnace Do not connect to a down flow furnace Do not connect ductwork so that a reverse flow is possible Operate the gas oil electric furnace periodically to ensure it will operate satisfactorily when needed Certified for installation with the ductwork configurat...

Страница 11: ... only have one appliance per chimney and it is not permissible to connect your Hitzer Energy Master II furnace to a chimney that is servicing another appliance Flue Requirements It is required to have a chimney that is built according to the chimney manufacturer s specifications and meets local building codes It is also required to have your chimney inspected and cleaned by a certified chimney pro...

Страница 12: ...our draft A few of these include wind speed and direction obstructions diverting winds barometric pressure and humidity This is why it is essential to have a barometric damper and carbon monoxide detectors alarms installed and working properly Power Vent System A Hitzer approved power vent may be used in place of a chimney BE SURE TO READ YOUR POWER VENTER INSTALLATION AND OPERATION INSTRUCTION MA...

Страница 13: ...he properly constructed and in good top of the fire box When the door is condition Chimney must be at least 15 opened oxygen combines with gases high and exceed the roof a minimum of and ignites 3 feet unless using Power Vent System WARNING Risk of Fire WARNING Over Fire Unit Comply with all minimum clearances to Do NOT over fire your unit combustibles as specified This will cause warping of fire ...

Страница 14: ... hole to read the chimney draft Adjust the barometric damper so that your manometer reads between 03 and 06 inches of water column following the instructions provided with the damper Do not run at a draft above 06 inches of water column as this could cause your stoker to over fire Over firing can cause a dangerous fire hazard It would be best to set it with a manometer if available The settings on...

Страница 15: ...amount of coal burned ash content of the coal the burn rate and draft of the chimney Allow stoker to run out of coal go out and cool down Remove chimney connector pipes and check and remove any fly ash accumulation This will mainly be at the bottom of elbows and horizontal runs Remove all fly ash from heat exchanger plates inside and below the flue collar and on the floor of the stoker around the ...

Страница 16: ...Page 16 VI Troubleshooting ...

Страница 17: ...rmined by the capacity and condition of the battery and the amount of heat needed Some generators will also work however the output of either must be a pure sine wave Other outputs can cause the Coal Troll Digital to not work You may also contact your Hitzer dealer or Hitzer Inc for questions or more information regarding stove installation and operation Hitzer Inc 269 E Main St Berne IN 46711 260...

Отзывы: