– 115 –
CHECKING THE REFRIGERATING CYCLE
1. Troubleshooting procedure (No operation, No heating, No cooling)
Connect U,V,W phase leads to the
power module again and operate the
air conditioner.
Gas leaks.
Repair and seal refrigerant.
Is the self-diagnosis lamp mode as
shown on the right?
YES
Gas leaking
(less than 4kg/cm
2
G)
(less than 0.39 MPaG)
Normal
(0.39-0.98 MPaG)
(4-10 kg/cm
2
G)
Perform a final check of operation.
When the
self-diagnosis lamp
lights in the same
condition as above.
The compressor is defective. Replace it
and seal refrigerant.
If the compressor checker for an
inverter type air conditioner is
available, re-check using it.
( )
(JUDGING BETWEEN GAS LEAKAGE AND
COMPRESSOR DEFECTIVE)
Blinking
off
Time until the
lamp lights
Approx. 10 seconds
Approx.
10
seconds
Approx.
10
seconds
Within
Approx.
30
seconds
Compressor
Compressor
Gas
leakage
Possible
malfunctioning
part
LD301
Self-
diagnosis lamp
Lighting mode
Blinks
2 times
Blinks
3 times
Blinks
4 times
Blinks
5 times
Blinks
6 times
Blinks
8times
Stop to operate and check the gas
pressure in balancing mode.
Checking the system power module
Содержание Summit RAC-50YH5
Страница 32: ... 30 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS 50FH5 INDOOR UNIT 47 5 60 205 220 ...
Страница 38: ...MODEL RAS 50FH5 CIRCUIT DIAGRAM 39 ...
Страница 39: ...CIRCUIT DIAGRAM MODEL RAC 50YH5 41 ...
Страница 41: ... 44 MODEL RAS 50FH5 RECEIVING P W B MARKING ON P W B COMPONENT SIDE SOLDERING SIDE ...
Страница 42: ... 45 MODEL RAC 50YH5 MAIN P W B Marking on P W B E D I S T N E N O P M O C ...
Страница 45: ... 51 ...
Страница 91: ... 103 SELF DIAGNOSIS LIGHTING MODE MODEL RAC 50YH5 ...
Страница 109: ... 121 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS 50FH5 ...
Страница 113: ...RAS 50FH5 RAC 50YH5 HITACHI PM NO 0364E Printed in Malaysia ...