Chapter 4
Explanation of Functions
4-146
Register No.
Function name
Function code
R/W
Monitoring and setting items Data resolution
Data
resolution
1236h
(Reserved)
-
-
Inaccessible
-
1237h
(Reserved)
-
-
Inaccessible
-
1238h
Jog frequency setting
A038
R/W "Start frequency" to 999
0.01 [Hz]
1239h
Jog stop mode
A039
R/W
0 (free-running after jogging stops [disabled during
operation])
1 (deceleration and stop after jogging stops [disabled
during operation])
2 (DC braking after jogging stops [disabled during
operation])
3 (free-running after jogging stops [enabled during
operation])
4 (deceleration and stop after jogging stops [enabled
during operation])
5 (DC braking after jogging stops [enabled during
operation])
-
123Ah
(Reserved)
-
-
-
123Bh
Torque boost method selection
A041
R/W 0 (manual torque boost), 1 (automatic torque boost)
-
123Ch
Manual torque boost value
A042
R/W 0 to 200
0.1 [%]
123Dh
Manual torque boost frequency
adjustment
A043
R/W 0 to 500
0.1 [%]
123Eh
V/F characteristic curve
selection, 1st motor
A044
R/W
0 (VC), 1 (VP), 2 (free V/f), 3 (sensorless vector control), 4
(0Hz-range sensorless vector), 5 (vector with sensor)
-
123Fh
V/f gain setting
A045
R/W 20 to 100
1 [%]
1240h
Voltage compensation gain
setting for automatic torque
boost, 1st motor
A046
R/W 0 to 255
1 [%]
1241h
Slippage compensation gain
setting for automatic torque
boost, 1st motor
A047
R/W 0 to 255
1 [%]
1242h
to1244h
(Reserved)
-
-
Inaccessible
-
1245h
DC braking enable
A051
R/W 0 (disabling), 1 (enabling), 2 (set frequency only)
-
1246h
DC braking frequency setting
A052
R/W 0 to 40000
0.01 [Hz]
1247h
DC braking wait time
A053
R/W 0 to 50
0.1 [sec.]
1248h
DC braking force during
deceleration
A054
R/W 0 to 100
1 [%]
1249h
DC braking time for
deceleration
A055
R/W 0 to 600
0.1 [sec.]
124Ah
DC braking/edge or level
detection for [DB] input
A056
R/W 0 (edge operation), 1 (level operation)
-
124Bh
DC braking force for starting
A057
R/W 0 to 100
1 [%]
124Ch
DC braking time for starting
A058
R/W 0 to 600
0.1 [sec.]
124Dh
DC braking carrier frequency
setting
A059
R/W 5 to 150
0.1 [kHz]
124Eh
(Reserved)
-
-
Inaccessible
-
124Fh
Frequency upper limit setting
A061 (high)
R/W 0 or "maximum frequency limit" to "maximum frequency" 0.01 [Hz]
1250h
Frequency lower limit setting
A061 (low)
R/W
0 or "maximum frequency limit" to "maximum frequency" 0.01 [Hz]
1251h
A062 (high)
R/W
1252h
Jump (center) frequency setting
1
A062 (low)
R/W
0 to 40000
0.01 [Hz]
1253h
A063 (high)
R/W
1254h
Jump (hysteresis) frequency
width setting 1
A063 (low)
R/W
0 to 1000
0.01 [Hz]
1255h
A064
R/W
1256h
Jump (center) frequency setting
2
A065 (high)
R/W 0 to 40000
0.01 [Hz]
1257h
Jump (hysteresis) frequency
width setting 2
A065 (low)
R/W
0 to 1000
0.01 [Hz]
1258h
A066
R/W
1259h
Jump (center) frequency setting
3
A067 (high)
R/W 0 to 40000
0.01 [Hz]
125Ah
Jump (hysteresis) frequency
width setting 3
A067 (low)
R/W
0 to 1000
0.01 [Hz]
125Bh
A068
R/W
125Ch
Acceleration stop frequency
setting
A069 (high)
R/W 0 to 40000
0.01 [Hz]
125Dh
Acceleration stop time
frequency setting
A069 (low)
R/W
0 to 600
0.1 [sec.]
125Eh
A070
R/W
Содержание SJ700-4000HFU2
Страница 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Страница 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Страница 70: ...Chapter 3 Operation 3 25 Memo ...
Страница 246: ...Chapter 5 Error Codes 5 11 Memo ...
Страница 254: ...Chapter 6 Maintenance and Inspection 6 7 Memo ...
Страница 280: ...Chapter 8 List of Data Settings 8 17 Memo ...