Chapter 4
Explanation of Functions
4-137
(vii) Writing data to multiple registers [10h]
This function writes data to sequential registers.
(Example)
When setting "3,000 Hz" as the Acceleration (1) time (F002) in the inverter at slave address "1":
Since register "1103h" and "1104h" to store the Acceleration (1) time (F002) have a data resolution of 0.01 seconds,
specify "300000" (493E0h) as the updating data to set "3,000 seconds".
If the function to write data to multiple registers cannot be executed normally, the inverter will return an exception
response. For details, see Item (viii), "Exception response."
(viii) Exception response
The master system requests the inverter (slave) to return a response upon reception of a query other than broadcasted
queries. The inverter must return the response that matches the query it has received. However, if an error is found in
a query, the inverter will return an exception response.
The exception response consists of the following fields:
Field configuration
Slave address
Function code
Exception code
CRC-16 code
Details of the field configuration are described below. The exception response in reply to a query includes a function
code that is the sum of "80h" and the function code specified by the query. The exception code in the exception
response indicates the content of the error.
Query
Field name
Sample setting
(hexadecimal)
1
Slave address (*1)
01
2
Function code
10
3
Starting register address (upper
digit) (*2)
11
4
Starting register address (lower
digit) (*2)
02
5
Number of registers (upper digit)
00
6
Number of registers (lower digit)
02
7
Number of data bytes (*3)
04
8
Updating data 1 (upper digit)
00
9
Updating data 1 (lower digit)
04
10
Updating data 2(upper digit)
93
11
Updating data 2(lower digit)
E0
12
CRC-16 code (upper digit)
9E
13
CRC-16 code (lower digit)
9F
*1 If this query is broadcasted, no inverter will return any response.
*2 Note that the starting register address is 1 less than the actual address of
the register to which the data is to be written first.
*3 As the number of bytes, do not specify the number of registers but the
number of bytes to be actually updated.
Response
Field name
Sample setting
(hexadecimal)
1
Slave address (*1)
01
2
Function code
10
3
Starting register address (upper
digit) (*2)
11
4
Starting register address (lower
digit) (*2)
02
5
Number of registers (upper digit)
00
6
Number of registers (lower digit)
02
7
CRC-16 code (upper digit)
E5
8
CRC-16 code (lower digit)
34
Function codes
Query
Exception response
01h
81h
03h
83h
05h
85h
06h
86h
0Fh
8Fh
10h
90h
Exception codes
Code
Description
01h
An unsupported function is specified.
02h
The specified address is not found.
03h
The specified data has an unacceptable format.
21h
The data to be written to a register exceeds the range of inverter
specifications.
22h
The inverter restricts the execution of the specified function:
- Rewriting a register that cannot be rewritten during the operation
- Issuing an Enter command during the operation (in undervoltage
status)
- Writing to a register during tripping (because of undervoltage)
- Writing to a read-only register (coil)
Содержание SJ700-4000HFU2
Страница 16: ...Contents Appendix Appendix A 1 Index Index Index 1 ...
Страница 44: ...Chapter 2 Installation and Wiring 2 23 Memo ...
Страница 70: ...Chapter 3 Operation 3 25 Memo ...
Страница 246: ...Chapter 5 Error Codes 5 11 Memo ...
Страница 254: ...Chapter 6 Maintenance and Inspection 6 7 Memo ...
Страница 280: ...Chapter 8 List of Data Settings 8 17 Memo ...