Chapter 4 Explanation of Functions
4.2.23 PID function
The PID function allows you to use the inverter for the process
control on fluid flow, airflow, and pressure.
To enable this function, specify "01 lenabled" or "02 inverted data
output enabled" for function "A071".
You can disable the PID function with an external signal during
the PID operation. For this purpose, assign function "23" (PID
terminal: disabling PID operation) to an intelligent input terminal.
Turning the PID terminal on disables the PID function and makes
the inverter perform the normal output.
With the PID function, you can limit the PID output according to
various conditions.
Refer to maximum frequency (4.2.10), frequency limiter (4.2.20),
PID rariation range (A078).
Item
Function code
Data or range of data
Description
00
Disabling the PID operation
01
Enabling the PID operation
PID Function Enable
A071
02
Enabling inverted-data output
PID proportional gain
A072
0.2 to 5.0
Proportional gain
PID integral time constant
A073
0.0 to 3600.(s)
Integrated gain
PID derivative gain
A074
0.00 to 100.0(s) Derivative
gain
PV scale conversion
A075
0.01 to 99.99
Scale for unit conversion of PID feedback
data
00
OI-L: 4 to 20 mA
01
O-L: 0 to 10 V
02 RS485
communication
03
Frequency command as pulse train
PV source setting
A076
10
Operation result (*1)
00
Disabling the inverted output
Output of inverted PID
deviation
A077
01
Enabling the inverted output (deviation
polarity inverted)
PID variation range
A078
0.0 to 100.0(%)
Range of PID data variation with
reference to the target value
00 Invalid
01
O-L : 0-10V
02
OI-L : 4-20mA
PID feed forward selection
A079
03
O2-L : -10-10V
PID deviation level setting
C044
0.0 to 100.0(%)
Level to determine the OD signal output
Off level of feedback
comparison signal
C052
0.0 to 100.0(%)
Level to determine the FBV signal output
Onlevel of feedback
comparison signal
C053
0.0 to 100.0(%)
Level to determine the FBV signal output
(*1) refer 4.2.12 Frequency operation function
(1) Basic configuration of PID control
fs
M
=
+
-
Kp
(
1+
+Td
・
S
)
1
Ti
・
S
Target value
0 to 10 V
4 to 20 mA
Deviation
(
ε
)
Feedback
0 to 10 V
4 to 20 mA
Operation
quantity
Normal control
by the inverter
Transducer
Sensor
+
+
Feed Forward invalid
0-10V
0-20mA
-10-10V
A001: Frequency source setting
A005: [AT] selection
A006: [O2] selection
A071: PID Function Enable
A072: PID proportional gain
A073: PID integral time constant
A074: PID derivative gain
A075: PV scale conversion
A076: PV source setting
A077: Output of inverted PID deviation
A078: PID variation range
A079: PID feed forward selection
d004: Process variable (PV), PID feedback
monitoring
C001 to C008: Terminal [1] to [8] functions
C021 to C025: Terminal [11] to [15] functions
C044: PID deviation level setting
C052: Off level of feedback comparison signal
C053: Onlevel of feedback comparison signal
Related code
Kp: Proportional gain Ti: Integral time Td: Derivative time s: Operator
ε
: Deviation
4 -
26
Содержание SJ700-055HFF2
Страница 15: ...Contents xiii Appendix Appendix A 1 Index Index Index 1 ...
Страница 17: ......
Страница 22: ......
Страница 43: ...Chapter 2 Installation and Wiring 2 21 ...
Страница 48: ......
Страница 51: ...Chapter 3 Operation 3 3 ...
Страница 63: ......
Страница 152: ...Chapter 4 Explanation of Functions 4 89 H034 H234 ...
Страница 161: ...Chapter 4 Explanation of Functions 4 98 ...
Страница 219: ...Chapter 4 Explanation of Functions 4 156 ...
Страница 232: ......
Страница 244: ......
Страница 252: ......
Страница 258: ...Chapter 7 Specifications SJ700 550 LFF2 LFUF2 5 Cable hole φ41 7 6 ...
Страница 260: ......