Chapter 2 Installation and Wiring
Symbol
Terminal name
Description
Electric property
Cont
a
c
t in
put
Functi
on
sel
e
cti
on
and l
o
gi
c sw
it
chi
n
g
PLC
Intelligent input
(common)
To switch the control logic between sink logic and source logic, change the
jumper connection of this (PLC) terminal to another terminal on the control
circuit terminal block.
Jumper terminals P24 and PLC for the sink logic; jumper terminals CM1
and PLC for the sink logic.
To use an external power supply to drive the contact inputs, remove the
jumper, and connect the PLC terminal to the external interface circuit.
11
12
13
14
15
Intelligent output
Select five of a total 51 functions, and assign these five functions to
terminals 11 to 15.
If you have selected an alarm code using the function "C062", terminals 11
to 13 or 11 to 14 are used exclusively for the output of cause code for alarm
(e.g., inverter trip). The control logic between each of these terminals and
the CM2 terminal always follows the sink or source logic.
Open colle
c
tor
o
u
tp
ut
S
tatu
s
and
factor
CM2
Intelligent output
(common)
This terminal serves as the common terminal for intelligent output terminals
[11] to [15].
Voltage drop between each
terminal and CM2 when
output signal is on: 4 V or
less
Maximum allowable
voltage: 27 VDC
Maximum allowable
current: 50 mA
Dig
it
a
l (co
n
ta
ct)
Rela
y cont
act outp
u
t
S
tatu
s
and
alarm
AL0
AL1
AL2
Intelligent relay
output
Select functions from the 43 available, and assign the selected functions to
these terminals, which serve as C contact output terminals.
In the initial setting, these terminals output an alarm indicating that the
inverter protection function has operated to stop inverter output.
(Maximum contact
capacity)
AL1-AL0: 250 VAC, 2 A
(resistance) or 0.2 A
(inductive load)
AL2-AL0: 250 VAC, 1 A
(resistance) or 0.2 A
(inductive load)
(Minimum contact capacity)
100 VAC, 10 mA
5 VDC, 100 mA
Analog
Analog i
nput
Sensor
TH
External
thermistor input
Connect to an external thermistor to make the inverter trip if an abnormal
temperature is detected.
The CM1 terminal serves as the common terminal for this terminal.
[Recommended thermistor properties]
Allowable rated power: 100 mW or more
Impedance at temperature error: 3k
Ω
The impedance to detect temperature errors can be adjusted within the
range 0
Ω
to 9,999
Ω
.
Allowable range of input
voltages
0 to 8 VDC
[Input circuit]
CM1
TH
Thermistor
1k
Ω
DC8V
10k
Ω
(3) Explanation of switch settings
The internal slide switch (SW1) is used to enable or disable the emergency stop function (the function
is disabled by factory setting).
* For the location of the slide switch, see page 2-9.
2 - 8
Содержание SJ700-055HFF2
Страница 15: ...Contents xiii Appendix Appendix A 1 Index Index Index 1 ...
Страница 17: ......
Страница 22: ......
Страница 43: ...Chapter 2 Installation and Wiring 2 21 ...
Страница 48: ......
Страница 51: ...Chapter 3 Operation 3 3 ...
Страница 63: ......
Страница 152: ...Chapter 4 Explanation of Functions 4 89 H034 H234 ...
Страница 161: ...Chapter 4 Explanation of Functions 4 98 ...
Страница 219: ...Chapter 4 Explanation of Functions 4 156 ...
Страница 232: ......
Страница 244: ......
Страница 252: ......
Страница 258: ...Chapter 7 Specifications SJ700 550 LFF2 LFUF2 5 Cable hole φ41 7 6 ...
Страница 260: ......