parameters A_42 and A_43. The manual boost is calculated as an addition to the
standard straight V/f line (constant torque curve).
NOTE:
Manual torque boost is not operational when sensorless vector control is in use.
Be aware that running the motor at a low speed for a long time can cause motor
overheating. This is particularly true when manual torque boost is ON, or if the motor
relies on a built-in fan for cooling.
NOTE:
Manual torque boost applies only to constant torque (A_44=00) and variable
torque (A_44=01) V/f control.
Voltage Gain –
Using parameter A_45 you
can modify the voltage gain of the inverter (see
graph at right). This is specified as a percent-
age of the full scale setting (Automatic Voltage
Regulation) AVR level in parameter F_03. The
gain can be set from 50% to 100%. It should be
adjusted in accordance with the motor specifi-
cations.
Sensorless Vector Control (SLV)
– This advanced torque control algorithm improves
torque performance at very low speeds—down to 0.5 Hz. Set parameter A_44=02 to
select SLV operation. The SLV algorithm must be tuned to match the characteristics of
the particular motor connected to your inverter. Simply using the default motor parame-
ters in the inverter will not work satisfactorily for these control methods. Chapter 4
discusses motor/inverter size selection and how to set the motor parameters either
manually or by using the built-in auto-tuning. Before using the sensorless vector control
methods, please refer to
“Auto-tuning for Sensorless Vector Control” on page 4–35
NOTE:
When the inverter is in SLV (sensorless vector) mode, use B_83 to set the carrier
frequency greater than 2.1 kHz for proper operation.
NOTE:
You must disable sensorless vector operation when two or more motors are
connected (parallel operation) to the inverter.
A 45
V
100%
50%
Hz
Voltage Gain
0
Содержание SJ100 Series
Страница 159: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 186: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 194: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 B ...
Страница 204: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 C ...
Страница 207: ...CE EMC Installation Guidelines Appendix C C 4 L1 L2 L3 PE M 3 SJ100 inverter with footprint type filter ...
Страница 208: ...SJ100 Inverter Appendix C C 5 L1 L2 L3 PE SJ100 inverter with book type filter M 3 ...