![Hitachi RWM-(H)FSN3E Скачать руководство пользователя страница 92](http://html.mh-extra.com/html/hitachi/rwm-h-fsn3e/rwm-h-fsn3e_technical-catalogue_2139430092.webp)
6 Working range
TCGB0070 rev.3 - 04/2012
92
6.1 Temperature range
MODEL
RWM-2.0
(H)FSN3E
RWM-3.0
(H)FSN3E
RWM-4.0
(H)FSN3E
RWM-5.0
(H)FSN3E
RWM-6.0
(H)FSN3E
RWM-8.0
(H)FSN3E
RWM-10.0
(H)FSN3E
Water temperature
ºC
Refer to the graphics for each case
Minimum flow rate
m
3
/h
0.5
0.9
1.0
1.1
1.2
2.0
2.2
Maximum flow rate
m
3
/h
2.2
2.6
3.3
3.6
3.6
4.7
4.8
Minimum installation water volume
l
28
28
38
46
55
76
79
Minimum allowable water pressure MPa
0.1
Maximum allowable water pressure MPa
0.3
6.1.1 Heating mode
Space heating
*
( )
*
( )
Heating space normal working area
(Water rule: 0.2 - 2.2)
Ambient
temperature
(ºC WB)
Water outlet
temperature
(ºC)
N O T E
(*): 2HP system only
(RAS- RWM-2.0(H)FSN3E).
Domestic Hot Water Tank heating
*
( )
Ambient
temperature
(ºC WB)
DHWT water
temperature
(ºC)
DHWT heating working area with combined
boiler and/or electric heater
DHWT heating normal working area
by air to water heat pump
(**)
N O T E
(*): 2HP system only
(RAS- RWM-2.0(H)FSN3E).
(**): DHWT maximum water temperature
default value by air to water heat pump
is 54ºC, but it depends on the field ins
-
tallation and the selected tank.