4 Capacity and selection
data
TCGB0070 rev.3 - 04/2012
80
4.3 Heating nominal points of interest
The following table shows the nominal heating capacity and coefficient of performance at the specified conditions:
Model
Indoor unit
RWM-
2.0(H)FSN3E
RWM-
3.0(H)FSN3E
RWM-
4.0(H)FSN3E
RWM-
5.0(H)FSN3E
RWM-
6.0(H)FSN3E
RWM-
8.0(H)FSN3E
RWM-
10.0(H)FSN3E
Outdoor unit
RAS-
2HVRN2
RAS-
3HVRNME-AF
RAS-
4H(V)RNME-AF
RAS-
5H(V)RNME-AF
RAS-
6H(V)RNME-AF
RAS-
8HRNME-AF
RAS-
10HRNME-AF
1) Conditions: Water in/out */35ºC
Out Temp, (DB/WB): 10/9ºC
CAP (kW)
5.3
7.7
10.3
12.7
15.0
20.6
25.3
COP
5.05
4.77
4.78
4.56
4.33
4.80
4.63
2) Conditions: Water in/out */45ºC
Out Temp, (DB/WB): 10/9ºC
CAP (kW)
4.9
7.3
9.6
12.0
14.3
19.3
23.9
COP
3.65
3.64
3.62
3.41
3.26
3.72
3.69
3) Conditions: Water in/out */55ºC
Out Temp, (DB/WB): 10/9ºC
CAP (kW)
4.4
6.3
8.5
10.4
13.4
17.2
21.2
COP
2.79
2.79
3.37
2.81
2.67
2.93
2.89
4) Conditions: Water in/out 30/35ºC
Out Temp, (DB/WB): 7/6ºC
CAP (kW)
5.1
7.5
9.8
12.0
14.0
19.6
24.0
COP
5.02
4.55
4.47
4.36
4.11
4.45
4.41
5) Conditions: Water in/out 40/45ºC
Out Temp, (DB/WB): 7/6ºC
CAP (kW)
4.7
7.1
9.2
11.3
13.3
18.4
22.6
COP
3.51
3.47
3.42
3.16
3.01
3.43
3.40
6) Conditions: Water in/out 47/55ºC
Out Temp, (DB/WB): 7/6ºC
CAP (kW)
4.2
6.2
8.1
10.1
12.6
16.2
20.2
COP
2.63
2.65
2.59
2.60
2.47
2.70
2.67
7) Conditions: Water in/out */35ºC
Out Temp, (DB/WB): 2/1ºC
CAP (kW)
4.7
7.1
9.0
10.9
12.4
17.9
21.9
COP
3.21
3.18
2.68
2.92
2.88
3.05
3.00
8) Conditions: Water in/out */45ºC
Out Temp, (DB/WB): 2/1ºC
CAP (kW)
4.4
6.7
8.5
10.2
11.7
16.9
20.5
COP
2.51
2.69
2.44
2.33
2.31
2.51
2.57
9) Conditions: Water in/out */55ºC
Out Temp, (DB/WB): 2/1ºC
CAP (kW)
3.8
5.9
7.5
9.6
10.6
14.6
18.5
COP
1.72
1.89
1.87
1.80
1.69
2.06
2.06
10) Conditions: Water in/out */35ºC
Out Temp, (DB/WB): -7/-8ºC
CAP (kW)
4.0
6.4
7.6
9.0
9.4
14.8
18.0
COP
2.65
2.51
2.42
2.40
2.34
2.63
2.61
11) Conditions: Water in/out */45ºC
Out Temp, (DB/WB): -7/-8ºC
CAP (kW)
3.8
6.0
7.1
8.3
8.7
14.2
16.6
COP
2.10
2.07
2.14
1.92
1.81
2.17
2.16
12) Conditions: Water in/out */55ºC
Out Temp, (DB/WB): -7/-8ºC
CAP (kW)
3.0
5.3
5.9
7.7
7.9
11.8
15.4
COP
1.62
1.65
1.55
1.55
1.46
1.73
1.72
N O T E
• CAP: Nominal heating capacity (kW).
• COP: Coefficient of performance.
The table above shows the capacity data in integrated values (with defrost factor included).