![Hitachi RWM-(H)FSN3E Скачать руководство пользователя страница 58](http://html.mh-extra.com/html/hitachi/rwm-h-fsn3e/rwm-h-fsn3e_technical-catalogue_2139430058.webp)
TCGB0070 rev.3 - 04/2012
58
3 General data
Model
RWM-8.0(H)FSN3E
RWM-10.0(H)FSN3E
Electrical power supply
-
3N~ 400V 50Hz
3N~ 400V 50Hz
Pump input power
W
250
260
Electric hea-
ter power
3 kW (step 1/ step 2/ step 3)
kW
-
-
6 kW (step 1/ step 2/ step 3)
kW
-
-
9 kW (step 1/ step 2/ step 3)
kW
3.0/6.0/9.0
3.0/6.0/9.0
Maximum electrical power consumption
(1~ / 3N~)
A
-/23
-/23
Nominal water flow (condition
)
m³/h
3.4
4.1
Outer
dimensions
Height
mm
890
Width
mm
670
Depth
mm
360
Net weight
kg
81
85
Packaging dimensions
m³
0.46
0.46
Sound pressure level
dB (A)
29
29
Refrigerant
-
R410A
Refrigerant pipe connection
-
Flare nut connection
Dimensions
Liquid pipe
mm
Ø9,53 (3/8”)
Ø12,7 (3/8”)
Gas pipe
mm
Ø25,4 (1”)
Ø25,4 (1”)
Water pipe connection
-
Shutdown valves (factory supplied)
Dimensions
Inlet
mm
G 1-1/4” (male)
G 1-1/4” (male)
Outlet
mm
G 1-1/4” (male)
G 1-1/4” (male)
Water pipe diameter (recommended)
mm
Ø28
Ø28
Expansion vessel volume
l
10.0
Color
-
White (RAL 9016)
N O T E
The sound pressure level is measured at 1 meter distance from the unit’s front surface with the pump running at
speed 2. This data is measured in an anechoic chamber, so reflected sound should be taken into consideration
when installing the unit.