2 Features and benefits
TCGB0070 rev.3 - 04/2012
46
Maximum/minimum water temperature setting for space protection by Installer mode
•
Heating circuit minimum/maximum temperature limits selection by installer: The installer will limit the space heating
temperature set-point in order to prevent excessively high or low temperatures.
Outdoor ambient temperature (ºC)
Water outlet temperature
set point ºC
Tmaxh
n
Tminh
n
Minimum water temp
Maximum water temp
Water temperature setting example
Outdoor ambient temperature(ºC)
Water outlet temperature
set-point (ºC)
Minimum water temperature
Maximum water temperature
Example of water temperature setting
N O T E
Very useful when water calculation type selected is by gradient
•
Cooling circuit minimum/maximum temperature limits selection by installer: The installer will limit the space cooling
temperature set-point in order to prevent excessively high or low temperatures.
Outdoor ambient temperature (ºC)
Water Outlet temperature
set point ºC
Minimum water temp
Maximum water temp
Ts
n
Tmax
c
n
Tmin
c
n
Water temperature setting example
Outdoor ambient temperature(ºC)
Water outlet temperature
set-point (ºC)
Minimum water temperature
Maximum water temperature
Example of water temperature setting
N O T E
• Very useful for refreshing floor protection.