10 Electrical wiring
TCGB0070 rev.3 - 04/2012
143
10
10.3 Common wiring
C A U T I O N
All the field wiring and electrical components must comply with local codes.
10.3.1 Electrical wiring between outdoor and indoor unit
-
Connect the electrical wires between the indoor unit and the outdoor unit, as shown in the next diagram.
-
Follow the local codes and regulations when performing the electrical wiring.
-
Use twist pair wires (more than 0.75 mm²) for operation wiring between outdoor unit and indoor unit.
-
Use 2-core wires for the operating line (Do not use wire with more than 3 cores).
-
Use shielded wires for intermediate wiring to protect the units from noise obstacle and sizing in compliance with
local codes.
-
In the event that a conduit tube for field-wiring is not used, fix rubber bushes to the panel with adhesive.
-
All the field wiring and equipment must comply with local and international codes.
C A U T I O N
Pay attention to the connection of the operating line. Incorrect connection may cause PCB failure.
RAS-3~6HVRNME-AF
RAS-4~6HVRNME-AF
Indoor Unit
RWM-4~6FSN3E
Indoor Unit
RWM-3~6FSN3E
Outdoor unit
RAS-(4-10)HRNME-AF
Outdoor unit
RAS-2HVRN2
RAS-(3-6)HVRNME-AF
Operating Line
(Twisted shielded pair
cable or shielded pair
cable)
DC5V (Non-Pole Trans-
mission, H-LINK system)
Operating Line
(Twisted shielded pair cable or shielded pair
cable)DC5V (Non-Pole Transmission, H-LINK
system)
Indoor unit
RWM-(2.0-6.0)FSN3E
Indoor unit
RWM-(4.0-10.0)FSN3E
TB
:
Terminal Board
CB
:
Circuit Breaker
ELB
:
Earth Leakage Breaker
:
Internal Wiring
:
Field Wiring
:
Field-Supplied
1,2
:
Outdoor-Indoor connection
N O T E
The power supply must be connected to the outdoor unit and indoor unit separately.