4 ELECTRICAL DATA
4.1 CONSIDERATIONS
Key words:
•
U: Power supply.
•
PH: Phase.
•
IPT: Total input power.
•
STC: Starting current: Less than maximum current.
•
RNC: Running current.
•
MC: Maximum current.
?
N O T E
• Heating conditions: Inlet/outlet water temperature: 30/35 ºC ; Outdoor ambient temperature (DB/WB): 7/6 ºC
• The compressor data shown in the tables below are based on a combined capacity of 100% of the power supplied.
• The “Maximum current” shown in the above table is the maximum total unit running current at the following conditions:
- Supply voltage: 90% of the rated voltage.
- Unit capacity: 100% at maximum operating conditions.
• The power supply cables must be sized to cover this maximum current value.
•
Specifications in these tables are subject to change without notice in order that Hitachi may bring the latest innovations to their customers.
• Please refer to the general information, cautions and notes regarding protective devices (CB, ELB) throughout the
“7 Electrical and control settings”
chapter.
ELECTRICAL DATA
PMML0575 rev.2 - 03/2022
24