Output terminals (Default output functions)
Mixing valve for Circuit 2
The mixing valve is controlled to maintain the second heating temperature at the second heating temperature set point. The control
system decides how much to open or close the mixing valve to achieve the desired position of the valve.
24
25
26
M
(C)
(O)
(N)
Brown
Black
Blue
Mixing Valve
(Circuit 2)
Terminal
Name
Description
24
C
Close
25
O
Open
26
N
Neutral
Valve requirements:
•
Power supply: 230V AC 50Hz
•
Maximum running current: 100mA
Water pump 2 Circuit 2
In case of a second circuit installation (second temperature level) the secondary pump is the circulating pump for the second heating
temperature.
26
(N)
M
27
(L)
Water pump II
(Circuit 2)
Pump requirements:
•
Power supply: 230V AC 50Hz
•
Maximum running current: 500mA (An auxiliary relay must
be installed in case of high consumption of the water pump).
Electrical heater DHWT output
In those cases where a DHW tank is installed with an electrical heater, the Air to Water heat pump can activate the electric heater of
the tank when the heat pump cannot achieve the required DHW temperature by itself.
(N)
31
Electrical
Heater
DHWT (EH
4
)
(L)
30
≤ 3kW
!
C A U T I O N
When using a DHW tank other than those from Hitachi, the maximum connectable heater load is 3 kW (connected to TB2 terminals 30-31).
3 Way valve for DHW tank output
YUTAKI units can be used to heat DHW. The signal is used on a 3-way motorized diverting valve and to provide control of supply
water flow (water flow for space heating when there is no signal, and water flow for DHW when signal is ON)
M
(L)
32
(C)
Brown
Black
Blue
33
34
3WV / DHW
DHWT
Valve requirements:
•
Power supply: 230V AC 50Hz
•
Maximum running current: 100mA
ELECTRICAL AND CONTROL SETTINGS
PMML0575 rev.2 - 03/2022
108