12 TROUBLESHOOTING
?
N O T E
•
(o): Option configurable from Unit controller. This alarm will be displayed if the system has been configured.
• o: Default. This alarm will be displayed in the Unit controller.
• –: No applicable.
12.1 ALARM CODE INDICATION ON REMOTE CONTROL SWITCH (PC-ARFH1E)
Alarm
indication
Alarm code
12.1.1 Alarms for Indoor units
Alarm
Code
Retry
Stop
Code
YUTAKI
S/SC
YUTAKI
S80
YUTAKI
M
Origin
Detail of Abnormality
Main Factors
3
-
o
o
o
Communication
Transmission Alarm (Not outdoor unit
detected)
Loose, disconnected, broken or
short-circuited connector
11
-
o
o
o
Indoor
Water inlet thermistor abnormally
(THMwi)
Loose, disconnected, broken or
short-circuited connector
12
-
o
o
o
Indoor
Water outlet thermistor abnormally
(THMwo)
Loose, disconnected, broken or
short-circuited connector
13
–
o
o
o
Indoor
Indoor Liquid Pipe Temp Thermistor
Abnormality (THMl)
Loose, disconnected, broken or
short-circuited connector
14
–
o
o
o
Indoor
Indoor Gas Pipe Temperature
Thermistor Abnormality (THMg)
Loose, disconnected, broken or
short-circuited connector
15
-
(o)
(o)
(o)
Indoor
Water Circuit 2 thermistor abnormally
(THMwo2)
Loose, disconnected, broken or
short-circuited connector
16
-
(o)
(o)
(o)
Indoor
Water DHW thermistor abnormally
(THMdhwt)
Loose, disconnected, broken or
short-circuited connector
17
-
(o)
(o)
(o)
Indoor
Auxiliary sensor 2 thermistor
abnormally (THMaux2)
Loose, disconnected, broken or
short-circuited connector
18
-
(o)
(o)
(o)
Indoor
Auxiliary sensor 1 thermistor
abnormally (THMaux1)
Loose, disconnected, broken or
short-circuited connector
19
-
o
-
-
Indoor
Water Plate HEX pipe thermistor
abnormally (THMwohp)
Loose, disconnected, broken or
short-circuited connector
19
-
o
-
Indoor
Suction R134a pipe thermistor
abnormally (THMs)
Loose, disconnected, broken or
short-circuited connector
23
-
o
-
Indoor
Discharge R134a pipe thermistor
abnormally (THMd)
Loose, disconnected, broken or
short-circuited connector
25
-
(o)
(o)
(o)
Indoor
Auxiliary sensor 3 thermistor
abnormally (THMaux3)
Loose, disconnected, broken or
short-circuited connector
40
-
o
o
o
Indoor
Incorrect LCD setting
Current LCD configuration does not
allow proper operation
TROUBLESHOOTING
PMML0575 rev.2 - 03/2022
314