6 Electrical wiring
5.2 DRAIN PIPE CONNECTION
1
The position of the drain pipe connection is shown below.
Common
Drain Piping
2
Prepare a polyvinyl chloride pipe with a 32mm outer diameter.
3
Fasten the tubing to the drain hose with an adhesive and the factory-
supplied clamp. The drain piping must be performed with a down-
slope pitch of 1/25 to 1/100.
4
Do not apply excessive force to the Drain Pipe connection. It could
cause a damage.
5
Do not use a bent or twisted Drain Hose. It will cause water leakage.
Gradient of Drain piping
m
ax.
850 mm
1/25~1/100
Down Slope
6
Insulate the drain pipe after connecting the drain hose. Do not use
adhesive between the Drain Pipe Connection and the
Drain Pipe Connection
Hose Band (Accessory)
Do not use adhesive
Vinyl Chloride VP25
(Field Supplied)
Use Vinyl Chloride
type adhesive
Drain Hose
(Accessory)
Hose Band
(Accessory)
Insulation
(Field supplied)
6 ELECTRICAL WIRING
6.1 GENERAL
D A N G E R
• Turn off the main power switch to the indoor unit and the outdoor
unit before electrical wiring work or a periodical check is per-
formed.
• Check to ensure that the indoor fan and the outdoor fan have
stopped before electrical wiring work or a periodical check is per-
formed.
• Protect the wires, drain pipe, electrical parts, etc. from rats or oth-
er small animals. If not protected, rats may gnaw at unprotected
parts and at the worst, a fire will occur.
C A U T I O N
• Use twisted shielded pair cable or shield pair cable for transmis-
sion wires between the indoor and the outdoor units, and connect
the shielded part to the earth screw in the electrical box of the
indoor unit as shown below.
• Wrap the field supplied insulation around the wires, and plug the
wiring connection hole with the seal material to protect the prod-
uct from any condensate water or insects.
• Tightly secure the wires with the cord clamp inside the indoor unit.
• Lead the wires through the knockout hole in the side cover when
using conduit.
• Secure the cable of the remote control switch using the cord
clamp inside the electrical box.
General Check
1
make sure that the field-selected electrical components (main power
switches, circuit breakers, wires, conduit connectors and wire termi-
nals) have been properly selected. make sure that the components
comply with National Electrical Code (NEC).
2
Check to ensure that the power supply voltage is 10% of the
rated voltage.
3
Check the capacity of the electrical wires. If the power source capac-
ity is too low, the system cannot be started due to the voltage drop.
4
Check to ensure that the ground wire is connected.