3
PmmL0231A rev. 0 - 02/2011
2 Name of parts
ENGLISH
2 NAME Of PARTS
RCI
No.
Part Name
1
Fan
2
Fan motor
3
Heat Exchanger
4
Distributor
5
Expansion Valve
6
Electric Control Box
7
Gas refrigerant Connection
8
Liquid refrigerant Connection
9
Drain Pipe Connection
10
motor for Drain Discharge mechanism
11
Float Switch
12
Drain Pan
13
Panel P-N23WA
14
Air Filter
15
Air Outlet
16
Air Inlet
17
Strainer
18
Air Inlet Grille
19
Cover for Corner Pocket
3 UNITS INSTALLATION
D A N G E R
• Check to ensure that the accessories are packed with the indoor unit.
• Do not install the indoor units outdoors. If installed outdoors, an
electric hazard or electric leakage will occur.
• Consider the air distribution from each indoor unit to the space of
the room, and select a suitable location so that uniform air tem-
perature in the room can be obtained. It is recommended that the
indoor units be installed 2.3 to 3 meters from the floor level. If the
unit is installed higher than 3 meters, it is also recommended that
a fan be utilised to obtain uniform air temperature in the room.
• Avoid obstacles which may hamper the air intake or the air dis-
charge flow.
• Pay attention to the following points when the indoor units are
installed in a hospital or other places where there are electronic
waves from medical equipment, etc.
• Do not install the indoor units where electromagnetic wave is directly
radiated to the electrical box, remote control cable or remote control
switch.
• Prepare a steel box and install the remote control switch in it. Pre-
pare a steel conduit tube and wire the remote control cable in it.
Then connect the ground wire with the box and tube.
• Install a noise filter when the power supply emits harmful noises..
• This unit is exclusive non electrical heater type indoor unit. It is
prohibited to install a electrical heater in the field.
• Mount suspension bolts using M10 (W3/8) as size, as shown below:
I-Beam
Suspension Bolts
(W3/8 or m10)
For Concrete Slab
150~160mm
Sling Bolt
(W3/8 or m10)
Square washers
Wooden Bar
(60 mm to 90 mm
Square)
Steel
Concrete
Nuts
Anchor Bolt
Wooden Beam
• Do not put any foreign material into the indoor unit and check to ensure that none exist in the indoor unit before the installation and test
running. Otherwise a fire or failure, etc., may occur.