14.2.2
,QVWDOODWLRQORFDWLRQ
D A N G E R
•
3URYLGHDVXI¿FLHQWO\VWURQJIRXQGDWLRQ,IQRWWKHXQLWPD\IDOO
down and it may lead to injuries.
•
'RQRWLQVWDOOWKHXQLWZKHUHÀDPPDEOHJDVPD\EHJHQHUDWHGRU
ÀRZ,WPD\FDXVHD¿UH
Select the installation location as follows:
• (A) Minimum Space
• (B) Down Slope Pitch of Drain Pipe: 1/25 to 1/100
345mm
Min. 10mm
Down Slope Pitch:
1/25 to 1/100
Drain piping
Unit Height in
false ceiling
Clearance
• The sensing area for the motion sensor is shown in the
¿JXUHEHORZZKHQDSSO\LQJWKHPRWLRQVHQVRUNLWRSWLRQ
with the air panel.
Installation Height of Indoor Unit: h (m)
3.1
Sensing Area for Motion Sensor: øa (m)
$SSUR[
Motion Detection
Human Motion
Motion sensor
)URPÀRRUVXUIDFHP
φ
a
h
• Consider the air distribution from the indoor unit to the space
of the room, and select a suitable location so that uniform air
temperature in the room can be obtained.
•
'RQRWSODFHÀDPPDEOHPDWHULDOVLQWKHVHUYLFHVSDFHIRU
the indoor unit.
• Install the unit where there is no obstacles which may
hamper the suction air and discharged air.
• Do not install the unit near a door or a window where the
indoor unit may contact humid outside air. Otherwise, dew
condensation may occur.
•
,QFDVHWHPSHUDWXUHDQGKXPLGLW\LQVLGHWKHFHLOLQJH[FHHGV
&5+5XPLGLW\DSSO\DGGLWLRQDOLQVXODWLRQ
PDWHULDOVWRWKHH[WHUQDOVXUIDFHRIWKHLQGRRUXQLWWRDYRLG
dew condensation.
• If installing the indoor unit to a high ceiling, the warmed air
may stay around the ceiling during heating operation. Thus,
the parallel installing of a circulator is recommended.
•
'RQRWLQVWDOOWKHLQGRRUXQLWZKHUHWKHDLUÀRZIURPWKHDLU
outlet blows directly to the temperature detecting devices
such an alarm device or a control device. It may cause a
failure of an alarm device or a control device.
• For simultaneous operation of multiple units (twin, triple and
quad combination) , the units must be installed in the same
room and be operated under the same conditions. If the
room is partitioned by a wall, furniture or a curtain, etc., it
may cause an operation failure. Take care when rearranging
furniture or remodeling the room after installation as well.
ENGLISH
INDOOR UNIT INSTALLATION
PMML0416A rev.0 - 12/2015 - P5415720
17