12.2.2
Installation location
!
D A N G E R
• Provide a sufficiently strong foundation. If not, the unit may fall down and it may lead to injuries.
• Do not install the unit where flammable gas may be generated or flow. It may cause a fire.
Select the installation location as follows:
• (A) Minimum Space
• (B) Down Slope Pitch of Drain Pipe: 1/25 to 1/100
345mm
Min. 10mm
Down Slope Pitch:
1/25 to 1/100
Drain piping
Unit Height in
false ceiling
Clearance
• The sensing area for the motion sensor is shown in the figure below when applying the motion sensor kit (option) with the air
panel.
Installation Height of Indoor Unit: h (m)
3.1
Sensing Area for Motion Sensor: øa (m)
Approx. 8.5
Motion Detection
Human Motion
Motion sensor
From floor surface 0.8m
φ
a
h
• Consider the air distribution from the indoor unit to the space of the room, and select a suitable location so that uniform air
temperature in the room can be obtained.
• Do not place flammable materials in the service space for the indoor unit.
• Install the unit where there is no obstacles which may hamper the suction air and discharged air.
• Do not install the unit near a door or a window where the indoor unit may contact humid outside air. Otherwise, dew
condensation may occur.
• In case temperature and humidity inside the ceiling exceeds 30ºC/RH (Relative Humidity) 80%, apply additional insulation
materials to the external surface of the indoor unit to avoid dew condensation.
• If installing the indoor unit to a high ceiling, the warmed air may stay around the ceiling during heating operation. Thus, the
parallel installing of a circulator is recommended.
• Do not install the indoor unit where the airflow from the air outlet blows directly to the temperature detecting devices such an
alarm device or a control device. It may cause a failure of an alarm device or a control device.
• For simultaneous operation of multiple units (twin, triple and quad combination) , the units must be installed in the same room
and be operated under the same conditions. If the room is partitioned by a wall, furniture or a curtain, etc., it may cause an
operation failure. Take care when rearranging furniture or remodeling the room after installation as well.
ENGLISH
INDOOR UNIT INSTALLATION
PMML0549 rev.1 - 02/2021 - A10761230A
17
Содержание RCD-2.0FSR
Страница 2: ......