15.4 DIP SWITCH SETTING
1
Turn OFF all the power supply to the indoor and the outdoor
units before dip switch setting. If not, the setting is invalid.
2
The positions of dip switches on PCB are shown in the figure
below.
56:
'6:
'6:
21
'6:
21
56:
21
'6:
'6:
21
21
'6:
21
Indoor unit PCB
DSW4 (Unit model code setting)
DSW5 (Refrigerant cycle number setting)
RSW2 (Refrigerant cycle number setting)
DSW7 (Fuse recover)
DSW3 (Capacity code number setting)
RSW1 (Indoor unit number setting)
DSW6 (Indoor unit number setting)
DSW9 (Optional function setting)
3
The indoor unit number of all indoor units are not required.
The indoor unit number are set by the auto-address function.
If the indoor unit number setting is required, set the unit
number of all indoor units respectively and serially by
following setting position. It is recommended to assign a
number to each indoor unit from “1.” Though max 64 indoor
units per refrigerant cycle can be connected to H-LINK ll
System, available numbers range from 0 to 63. Therefore,
the applicable number for the 64th indoor unit shall be “0.”
For the centralized control, this setting is required.
Factory setting
DSW6 (Tens digit)
RSW2 (Units digit)
1 2 3 4 5 6
ON
0
9
8
7 6 5 4
3
2
1
?
N O T E
• For units supporting H-LINK II: the unit numbers can be set for
maximum 64 indoor units (No.0-63).
• For units supporting H-LINK: the units numbers can be set for
maximum 16 indoor units (No.0-15).
Example: set at number 16 unit
DSW6 (Tens digit)
RSW2 (Units digit)
1 2 3 4 5 6
ON
0
9
8
7 6 5 4
3
2
1
4
Capacity code setting (DSW3). No setting is required, due to
setting before shipment. This switch is used for setting the
capacity code which corresponds to the Horse Power of the
indoor unit.
Horsepower
0.8
1.0
1.5
Setting position
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
Horsepower
2.0
2.5
3.0
Setting position
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
Horsepower
4.0
5.0
6.0
Setting position
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
5
Unit Model Code Setting (DSW4). No setting is required. It is
for setting the model code of the indoor unit.
Factory setting
6
Refrigerant cycle number setting (RSW2 & DSW5). Setting
is required. Setting positions before shipment are all OFF.
Example: set at number 5 cycle
DSW5 (Tens digit)
RSW1 (Units digit)
1 2 3 4 5 6
ON
0
9
8
7 6 5 4
3
2
1
• For units supporting H-LINK II: the refrigerant cycle numbers can
be set for maximum 64 cycles (No.0-63).
• For units supporting H-LINK: the refrigerant cycle numbers can be
set for maximum 16 cycles (No.0-15).
7
Fuse recover (DSW7). In the case of applying high voltage
to the terminal 1 and 2 of TB2, the fuse (0.5A) on the PCB
is cut, firstly reconnect the wirings correctly to TB2, and then
turn on Number 1 pin.
Factory setting
High voltage
1
2
ON
1
2
ON
8
Optional function setting (DSW9). No setting is required.
Setting positions before shipment are all OFF.
Factory setting
?
N O T E
• The “■” mark indicates position of dip switches. Figures show
setting before shipment.
• When the unit number and the refrigerant cycle are set, record
the unit number and refrigerant cycle to facilitate maintenance
and servicing activities thereafter.
ELECTRICAL WIRING
PMML0549 rev.1 - 02/2021 - A10761230A
32