OUTDOOR UNIT
P5414950-rev.1
53
11. Safety and Control Device Setting
O
Compressor Protection
High Pressure Switch: This switch cuts out the
operation of the compressor when the discharge
pressure exceeds the setting.
O
Fan Motor Protection
When the thermistor temperature is reached to
the setting, motor output is decreased.
The other way, when the temperature becomes
lower, limitation is cancelled.
Model
RAS-3HVRNM2 RAS-4HVRNM2 RAS-5HVRNM2 RAS-6HVRNM2 RAS-7HVRNM2
For Compressor
Automatic Reset, Non-Adjustable
Pressure Switch
(each one for each compressor)
High
Cut-Out
MPa
4.15
-0.05
-0.15
4.15
-0.05
-0.15
4.15
-0.05
-0.15
4.15
-0.05
-0.15
4.15
-0.05
-0.15
Cut-In
MPa
3.20+0.15
3.20+0.15
3.20+0.15
3.20+0.15
3.20+0.15
Low
Cut-Out
MPa
0.30+0.05
0.30+0.05
0.30+0.05
0.30+0.05
0.30+0.05
Cut-In
MPa
0.20+0.03
0.20+0.03
0.20+0.03
0.20+0.03
0.20+0.03
Fuse
1
I
, 220/240V, 50Hz
1
I
, 220V, 60Hz
A
40
50
50
50
50
CCP Timer
Non-Adjustable
Setting Time
min.
3
3
3
3
3
For Condenser Fan Motor
Automatic Reset, Non-Adjustable
Internal Thermostat
(each one for each motor)
For Control Circuit
Fuse Capacity on PCB
A
5
5
5
5
5
All the installation work of the air conditioning is completed.
Deliver and describe to keep this “Installation & Maintenance Manual” to a user.