2-94
TC-12001
OUTDOOR UNIT
18
P5414950-rev.1
(8) The whole of the base of the outdoor unit
should be installed on a foundation. When
using vibration-proof mat, it should also be
positioned the same way.
:KHQLQVWDOOLQJWKHRXWGRRUXQLWRQD¿HOG
supplied frame, use metal plates to adjust
the frame width for stable installation as
shown in Fig. 5.9.
Fig. 5.9 Frame and Base Installation
Recommended Metal Plate Size (Field-Supplied)
Material: Hot-Rolled Mild Steel Plate (SPHC)
Plate Thickness: 4.5T
(5) The drain water is discharged during the
heating and defrosting operation. Choose
a place where well drainage is available, or
provide a drain ditch.
(6) When installing the unit on a roof or a
veranda, the drain water sometimes turns
to ice in a cold morning. Therefore, avoid
draining in an area where people often use
because it is slippery. If installing such
the area, provide a second drain pan and
perform the drainage.
(7) Use the drain boss set (Optional, DBS-26(L))
when the drain piping work is required to the
outdoor unit. Pay attention that the drain
boss set can not be used in a snow and a
cold area.
$OXPLQXP¿QVKDYHYHU\VKDUSHGJHV3D\
DWWHQWLRQWRWKH¿QVWRDYRLGDQ\LQMXU\
NOTE
Install the outdoor unit on a roof or in an area
where people except service engineers can not
touch the outdoor unit.
Drain Hole (4-
24)
Drain Hole (
26)
69
224
239
348
Position for Drain Boss
(Optional)
93.5
140
84
Front (Air Outlet Side)
(mm)
Base Width of Outdoor Unit
70mm
Frame Width 60mm
(Field-Supplied)
Frame
Incorrect
Outdoor Unit
is Unstable.
Metal Plate
100mm or more
Metal Plate
Correct
Frame
Base Width of Outdoor Unit
70mm
Outdoor Unit
is Stable.
120
410
560
70
70
20
4-C10
2-Long Hole
14
60
R
(mm)